| 2012-04-05 12:20:40 | FIRE DEPARTMENT REVIEW ***DENIED*** |
| | ADDRESS:3330 45TH STREET SUITE A |
| | PERMIT # 12030654 |
| | CONTRACTOR: CAREY CONSTRUCTION COMPANY |
| | PHONE: 561 746-1440 |
| | |
| | 1.) ADDRESS ON PLANS DOES NOT MATCH THE ADDRESS ON THE |
| | PERMIT APPLICATION. |
| | 2.) DESIGN SHALL CONFORM TO THE 2010 EDITION OF THE |
| | FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE FLORIDA |
| | EDITION OF NFPA 1 AND NFPA 101. |
| | 3.) ALL DEMOLITION WORK SHALL CONFORM TO THE |
| | REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION DEBRIS |
| | SHALL BE REMOVED FROM THE SITE DAILY. |
| | 4.) SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE |
| | INSTALLATION OR MODIFICATION OF THE FIRE SPRINKLER |
| | SYSTEM AND/OR FIRE ALARM SYSTEM. |
| | 5.) EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL |
| | BE PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING |
| | READING FIRE/SMOKE BARRIER?PROTECT ALL OPENINGS. |
| | CHARACTERS SHALL BE AT LEAST 4-INCHES IN HEIGHT AND |
| | HALF-INCH IN WIDTH. IDENTIFICATION SHALL BE SPACED NOT |
| | MORE THAN 15 FEET ON CENTER. REFERENCE SECTION 8.3.2.4 |
| | OF FLORIDA FIRE PREVENTION CODE ? NFPA 101 |
| | 6.) PENETRATIONS THROUGH A FIRE-RATED WALL ASSEMBLY |
| | SHALL BE PROTECTED BY A FIRESTOP SYSTEM OR DEVICE. |
| | REFERENCE SECTION 8.3.5.1 OF FLORIDA FIRE PREVENTION |
| | CODE ? NFPA 101 |
| | |
| | |
| | DERRICK L. DANIELS, BATTALION CHIEF |
| | WEST PALM BEACH FIRE RESCUE |
| | FIRE & LIFE SAFETY PLAN REVIEW |