| Plan Review Notes For Permit 12030654 |
| Permit Number |
12030654 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-06 15:12:24 | 12030654 | | | 3330 45TH ST #A | | | INTERIOR WAREHOUSE REMODEL | | | | | | PROVIDE AN ELECTRICAL PERMIT. PROVIDE A PANEL SCHEDULE | | | SHOWING RATING, SIZE AND WIRING METHOD FOR THE NEW | | | ELECTRICAL CIRCUITS. NEC 210.3 | | | A GFCI GENERAL PURPOSE RECEPTACLE MUST BE INSTALLED AT | | | AN ACCESSIBLE LOCATION FOR THE SERVICE OF HEATING, AIR | | | CONDITIONING, AND REFRIGERATION EQUIPMENT. NEC 210.63 | | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES | | | AS REQUIRED BY THE FLORIDA BUILDING CODE. SPACE CONTROL | | | FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS 13-415.ABC.1.3, | | | EXISTING BUILDING CODE 711.1 | | | | | | NOTE: | | | SEPARATE PERMITS AND PLANS ARE REQUIRED FOR THE FIRE | | | ALARM SYSTEM, VOICE AND DATA. | | | | | | | | | | | | ROBERT LECKY, CBO | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|