| Notes |
| Date |
Text |
| 2012-03-30 11:43:51 | 12030614 | | | 417 BUNKER ROAD | | | INTERIOR ELECTRIC | | | | | | VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND | | | GROUPED IN ONE LOCATION. THE SITE PLANS SUGGEST THIS | | | BUILDING MAY BE ALREADY SERVED FROM ANOTHER LOCATION. | | | NEC 230.2, 230.71 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | | | | ROBERT LECKY, CBO | | | PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|