2012-04-11 14:09:24PLAN DENIED
 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE OUTDOOR
 AIR CURB TIE DOWN TO ROOF.
 PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M)
 2) REFER TO SECTION 606.2.1 SUPPLY AIR ( DUCT DETECTORS
 )
 AND 606.4.1 SUPERVISION 2010 FBC (M)
 3) REFER TO SECTION 403.5 MECHANICAL VENTILATION
 2010 FLORIDA ENERGY CODE
 4) REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010
 FLORIDA ENERGY CODE