| 2012-04-11 14:09:24 | PLAN DENIED | | | 1) PROVIDE A DETAIL FROM THE ENGINEER ON THE OUTDOOR | | | AIR CURB TIE DOWN TO ROOF. | | | PER SECTION 301.12 WIND RESISTANCE 2010 FBC (M) | | | 2) REFER TO SECTION 606.2.1 SUPPLY AIR ( DUCT DETECTORS | | | ) | | | AND 606.4.1 SUPERVISION 2010 FBC (M) | | | 3) REFER TO SECTION 403.5 MECHANICAL VENTILATION | | | 2010 FLORIDA ENERGY CODE | | | 4) REFER TO SECTION 403.6.1 EQUIPMENT SIZING 2010 | | | FLORIDA ENERGY CODE | | | PLAN REVIEW BY HAROLD MOSER | | | 561- 805-6732 | | | [email protected] | | | |
|