| 2012-04-13 14:51:14 | GOOD MORNING JASON, | | | THE RAS 117 CALCULATIONS ARE OK. PLEASE PROVIDE 2 | | | COPIES WITH ORIGINAL SEAL AND SIGNATURE. PLEASE PROVIDE | | | 2 COPIES OF NOA. PLEASE PROVIDE FASTENER PULL OUT TEST | | | REPORT TAS 105 AS REQUIRED BY GENERAL LIMITATION #5 ON | | | LAST PAGE OF NOA (THIS IS REQUIRED BECAUSE IF PULL OUT | | | RESISTANCE IS LESS THAN THE INDICATED VALUE, THEN IT | | | WILL NOT BE ACCEPTABLE). | | | REGARDING THE 208FR SPECS I SUGGEST YOU TO CONTACT | | | TAMKO. PLEASE NOTICE THAT PAGE 8 OF THE NOA CALLS FOR | | | BASE INSULATION LAYER MINIMUM 1.5" THICK AND TOP | | | INSULATION LAYER MINIMUM 1/2" THICK. REGARDING THE | | | NUMBER OF PLY SHEETS THE NOA SAYS ONE OR MORE PLIES. | | | THIS IS WHAT I WILL ASK TAMKO FOR CLARIFICATION. | | | PLEASE CONTACT ME IF YOU HAVE ANY OTHER QUESTION, | | | SINCERELY, | | | | | | | | | | | | JULIO C. GOMEZ | | | CITY OF WEST PALM BEACH | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | DEVELOPMENT SERVICES DEPARTMENT | | | (561)805-6712 | | | |
|