2012-04-13 14:51:14GOOD MORNING JASON,
 THE RAS 117 CALCULATIONS ARE OK. PLEASE PROVIDE 2
 COPIES WITH ORIGINAL SEAL AND SIGNATURE. PLEASE PROVIDE
 2 COPIES OF NOA. PLEASE PROVIDE FASTENER PULL OUT TEST
 REPORT TAS 105 AS REQUIRED BY GENERAL LIMITATION #5 ON
 LAST PAGE OF NOA (THIS IS REQUIRED BECAUSE IF PULL OUT
 RESISTANCE IS LESS THAN THE INDICATED VALUE, THEN IT
 WILL NOT BE ACCEPTABLE).
 REGARDING THE 208FR SPECS I SUGGEST YOU TO CONTACT
 TAMKO. PLEASE NOTICE THAT PAGE 8 OF THE NOA CALLS FOR
 BASE INSULATION LAYER MINIMUM 1.5" THICK AND TOP
 INSULATION LAYER MINIMUM 1/2" THICK. REGARDING THE
 NUMBER OF PLY SHEETS THE NOA SAYS ONE OR MORE PLIES.
 THIS IS WHAT I WILL ASK TAMKO FOR CLARIFICATION.
 PLEASE CONTACT ME IF YOU HAVE ANY OTHER QUESTION,
 SINCERELY,
  
  
  
 JULIO C. GOMEZ
 CITY OF WEST PALM BEACH
 COMMERCIAL COMBINATION PLANS EXAMINER
 DEVELOPMENT SERVICES DEPARTMENT
 (561)805-6712
  