Plan Review Notes
Plan Review Notes For Permit 12030532
Permit Number 12030532
Review Stop B
Sequence Number 5
Notes
Date Text
2012-04-12 12:47:59RE-ROOF BUILDING REVIEW 5TH CHECKLIST:
 2010 FBC.
  
 ***NOTE: E-MAIL COPY OF THIS COMMENTS WERE SENT TO
 ROBERT BROWN (ASSISTANT BUILDING OFFICIAL) FOR HIS
 REVIEW. THIS IS THE 5TH TIME THAT THE RAS 117
 CALCULATIONS WERE REQUESTED.
  
 1- ENGINEER TO PROVIDE RAS 117 CALCULATIONS AS REQUIRED
 BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA 11-0601.08
 SUBMITED FOR THE STEEL DECK.
 ENGINEER CALCULATIONS SUBMITTED ARE NOT THE REQUESTED
 RAS 117 CALCULATIONS. ENGINEER NEEDS TO GET FAMILIAR ON
 HOW THE RAS 117 CALCULATIONS ARE DONE. THEN, THE
 ENGINEER NEEDS TO REVIEW THE SELECTED APPROVED ASSEMBLY
 FROM THE PRODUCT APPROVAL FOR THE STEEL DECK. AND,
 THEN, DO THE RAS 117 CALCULATIONS.
 (NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY GENERAL
 LIMITATION #9 CAN'T BE USED. SEE GENERAL LIMITATION #9
 ON LAST PAGE OF NOA SUBMITTED).
  
 2- ENGINEER TO TAKE INTO CONSIDERATION THAT ACCORDING
 TO SEC. 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE
 "C" NOT "B". NEED TO REVISE THE DESIGN PRESSURES
 CALCULATIONS SUBMITTED AT THIS TIME WHEN DOING THE RAS
 117 CALCULATIONS.
  
 3- PLEASE SUBMIT 2 COPIES OF THE NOA FOR THE STEEL DECK
 ALONG WITH THE SPECIFIC APPROVED ASSEMBLY TO BE
 INSTALLED. (DCA RULE 9N-3).
  
 4- A) ALL CALCULATIONS COMING FROM THE ENGINEER NEED
 ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY
 CHAPTER 471 FLORIDA STATUTE.
  
 B) ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION ON THE
 CALCULATIONS AS REQUIRED BY CHAPTER 471 FLORIDA
 STATUTES WHEN SUBMITTING CALCULATIONS FOR PUBLIC
 RECORDS.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712