| 2012-04-12 12:47:59 | RE-ROOF BUILDING REVIEW 5TH CHECKLIST: |
| | 2010 FBC. |
| | |
| | ***NOTE: E-MAIL COPY OF THIS COMMENTS WERE SENT TO |
| | ROBERT BROWN (ASSISTANT BUILDING OFFICIAL) FOR HIS |
| | REVIEW. THIS IS THE 5TH TIME THAT THE RAS 117 |
| | CALCULATIONS WERE REQUESTED. |
| | |
| | 1- ENGINEER TO PROVIDE RAS 117 CALCULATIONS AS REQUIRED |
| | BY GENERAL LIMITATION #7 ON LAST PAGE OF NOA 11-0601.08 |
| | SUBMITED FOR THE STEEL DECK. |
| | ENGINEER CALCULATIONS SUBMITTED ARE NOT THE REQUESTED |
| | RAS 117 CALCULATIONS. ENGINEER NEEDS TO GET FAMILIAR ON |
| | HOW THE RAS 117 CALCULATIONS ARE DONE. THEN, THE |
| | ENGINEER NEEDS TO REVIEW THE SELECTED APPROVED ASSEMBLY |
| | FROM THE PRODUCT APPROVAL FOR THE STEEL DECK. AND, |
| | THEN, DO THE RAS 117 CALCULATIONS. |
| | (NOTE: APPROVED ASSEMBLIES THAT ARE LIMITED BY GENERAL |
| | LIMITATION #9 CAN'T BE USED. SEE GENERAL LIMITATION #9 |
| | ON LAST PAGE OF NOA SUBMITTED). |
| | |
| | 2- ENGINEER TO TAKE INTO CONSIDERATION THAT ACCORDING |
| | TO SEC. 1609.4.3 THIS BUILDING IS LOCATED ON EXPOSURE |
| | "C" NOT "B". NEED TO REVISE THE DESIGN PRESSURES |
| | CALCULATIONS SUBMITTED AT THIS TIME WHEN DOING THE RAS |
| | 117 CALCULATIONS. |
| | |
| | 3- PLEASE SUBMIT 2 COPIES OF THE NOA FOR THE STEEL DECK |
| | ALONG WITH THE SPECIFIC APPROVED ASSEMBLY TO BE |
| | INSTALLED. (DCA RULE 9N-3). |
| | |
| | 4- A) ALL CALCULATIONS COMING FROM THE ENGINEER NEED |
| | ENGINEER'S ORIGINAL SEAL AND SIGNATURE AS REQUIRED BY |
| | CHAPTER 471 FLORIDA STATUTE. |
| | |
| | B) ENGINEER NEEDS TO PROVIDE ALL HIS INFORMATION ON THE |
| | CALCULATIONS AS REQUIRED BY CHAPTER 471 FLORIDA |
| | STATUTES WHEN SUBMITTING CALCULATIONS FOR PUBLIC |
| | RECORDS. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |