Plan Review Notes
Plan Review Notes For Permit 12030532
Permit Number 12030532
Review Stop B
Sequence Number 4
Notes
Date Text
2012-04-06 15:25:45RE-ROOF FOURTH BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609. SEE GENERAL LIMITATION #9
 ON LAST PAGE OF NOA.
  
 2- NEED TO SPECIFY APPROVED ASSEMBLY WITH GENERAL
 LIMITATION #7 AND NEED SIGNED AND SEALED RAS 117
 CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7.
 ***NOTE: CALCULATIONS SUBMITTED FROM ECS FLORIDA LLC
 ARE NOT THE RAS 117 CALCULATIONS. ENGINEER FROM ECS
 FLORIDA NEEDS TO REVIEW SELECTED ASSEMBLY FROM NOA FOR
 STEEL DECKS AND THEN PROVIDE THE RAS 117 CALCULATIONS.
 COORDINATE WITH ITEM #1 ABOVE.
 ALSO, ENGINEER TO USE CURRENT CODE 2010 FBC.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712