| 2012-04-06 15:25:45 | RE-ROOF FOURTH BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED | | | APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL | | | LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE | | | LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE | | | DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN | | | PRESSURES OF FBC SEC. 1609. SEE GENERAL LIMITATION #9 | | | ON LAST PAGE OF NOA. | | | | | | 2- NEED TO SPECIFY APPROVED ASSEMBLY WITH GENERAL | | | LIMITATION #7 AND NEED SIGNED AND SEALED RAS 117 | | | CALCULATIONS AS REQUIRED BY GENERAL LIMITATION #7. | | | ***NOTE: CALCULATIONS SUBMITTED FROM ECS FLORIDA LLC | | | ARE NOT THE RAS 117 CALCULATIONS. ENGINEER FROM ECS | | | FLORIDA NEEDS TO REVIEW SELECTED ASSEMBLY FROM NOA FOR | | | STEEL DECKS AND THEN PROVIDE THE RAS 117 CALCULATIONS. | | | COORDINATE WITH ITEM #1 ABOVE. | | | ALSO, ENGINEER TO USE CURRENT CODE 2010 FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|