Plan Review Notes
Plan Review Notes For Permit 12030532
Permit Number 12030532
Review Stop B
Sequence Number 3
Notes
Date Text
2012-03-29 16:57:59RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609.
  
 2- NEED ASSEMBLY WITH GENERAL LIMITATION #7 AND NEED
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712