2012-03-26 11:08:14RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FBC.
  
 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED
 APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL
 LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE
 LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE
 DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN
 PRESSURES OF FBC SEC. 1609.
  
 2- NEED ASSEMBLY WITH GENERAL LIMITATION #7 AND NEED
 SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY
 GENERAL LIMITATION #7.
  
 3- REVISE THE RAS 117 CALCULATIONS SUBMITTED FOR THE
 WOOD DECK. NEED TO REVISE THE DESIGN PRESSURES AS
 CALCULATED BY FBC 2010 WHICH IS THE CURRENT CODE THAT
 WENT INTO EFFECT ON MARCH 15 2012.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER