| Plan Review Notes For Permit 12030532 |
| Permit Number |
12030532 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-03-26 11:08:14 | RE-ROOF BUILDING REVIEW COMMENTS. | | | 2010 FBC. | | | | | | 1- STEEL DECK NOA 11-0601.08 SUBMITTED: THE SELECTED | | | APPROVED ASSEMBLY ON PAGE 6 AND 7 IS LIMITED BY GENERAL | | | LIMITATION #9. THIS ASSEMBLY CAN'T BE USED BECAUSE | | | LIMITATION #9 DOESN'T ALLOW NAIL ENHANCING AND THE | | | DESIGN PRESSURES ARE TOO LOW TO MEET THE DESIGN | | | PRESSURES OF FBC SEC. 1609. | | | | | | 2- NEED ASSEMBLY WITH GENERAL LIMITATION #7 AND NEED | | | SIGNED AND SEALED RAS 117 CALCULATIONS AS REQUIRED BY | | | GENERAL LIMITATION #7. | | | | | | 3- REVISE THE RAS 117 CALCULATIONS SUBMITTED FOR THE | | | WOOD DECK. NEED TO REVISE THE DESIGN PRESSURES AS | | | CALCULATED BY FBC 2010 WHICH IS THE CURRENT CODE THAT | | | WENT INTO EFFECT ON MARCH 15 2012. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|