| Plan Review Notes For Permit 12030532 |
| Permit Number |
12030532 |
|
| Review Stop |
B |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-22 18:54:43 | RE-ROOF BUILDING REVIEW COMMENTS | | | 2010 FBC. | | | | | | 1- PROVIDE RAS 117 CALCULATIONS FOR NAIL ENHANCING AT | | | PERIMETER AND CORNER AREAS AS REQUIRED BY GENERAL | | | LIMITATION #7 ON LAST PAGE OF NOA 09-0820.11 SUBMITTED. | | | NEED NAIL ENHANCING TO MEET THE DESIGN PRESSURES | | | REQUIRED BY SEC. 1609 FBC. | | | | | | IF YOU HAVE ANY QUESTIONS, PLEASE CALL | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|