| 2012-04-05 10:34:37 | | | | | | | 1.) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG | | | THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A | | | MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE | | | DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR | | | AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC | | | 904.11.1. |
|