Plan Review Notes
Plan Review Notes For Permit 12030519
Permit Number 12030519
Review Stop FIRE
Sequence Number 2
Notes
Date Text
2012-04-05 10:34:37 
  
 1.) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG
 THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A
 MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE
 DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR
 AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC
 904.11.1.