| 2012-06-19 17:05:29 | RESIDENTIAL (R3) RENOVATION/ALTERATION SECOND BUILDING |
| | REVIEW COMMENTS. |
| | 2010 FBC. |
| | |
| | 1- ARCHITECT TO COORDINATE PLANS WITH THE REVISED |
| | ENERGY CALCULATIONS. NEED TO MEET THE MINIMUM |
| | REQUIREMENTS OF TABLE 402.1.1 OF 2010 FBC-ENERGY |
| | CONSERVATION. SEE COMMENTS ON ITEM 2 BELOW AND |
| | COORDINATE ACCORDINGLY. |
| | |
| | 2- ENERGY CALCULATIONS SUBMITTED (SEC. 107.2.1 CITY |
| | AMENDMENTS TO FBC): |
| | |
| | A) NEED TO MEET ALL THE MINIMUM REQUIREMENTS OF TABLE |
| | 402.1.1. REVISE THE WINDOWS AND DOORS FENESTRATION, |
| | CEILING INSULATION, WALL INSULATION, ETC. AND |
| | COORDINATE WITH REVISED ARCHITECT'S PLANS. SEE ITEM #1 |
| | ABOVE. |
| | |
| | B) PROVIDE COMPLETE AND CORRECT INFORMATION ON TOP OF |
| | FORM. SPECIFY BUILDER NAME. COORDINATE WITH OWNER. AND, |
| | REVISE THE JURISDICTION NO. THIS IS JURISDICTION 604700 |
| | NOT 661200. |
| | |
| | C) OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM. |
| | |
| | D) REVISE DOOR TYPE ON SHEET 3 OF 5. PRODUCT APPROVAL |
| | SUBMITTED FOR THE DOORS SHOW DOORS WITH MORE THAN 1/3 |
| | OF GLAZING ON THE DOOR. REVISE AS REQUIRED BY SEC. |
| | 405.5.3 OF 2010 FBC-ENERGY CONSERVATION. |
| | |
| | E) TAKING CEILING FAN CREDIT ON ITEM #15. ARCHITECT'S |
| | PLANS DON'T SHOW CEILING FAN. COORDINATE/REVISE AS |
| | REQUIRED. |
| | |
| | F) THERE IS NOT KITCHEN ON THIS BUILDING. REVISE |
| | INFORMATION ON SHEET 2 OF 5. |
| | |
| | G) REVISE AREAS SHOWN ON THE WINDOWS ON SHEET 3 OF 5 TO |
| | MATCH FLOOR PLANS AND ELEVATIONS SHOWN BY THE |
| | ARCHITECT. |
| | |
| | H) SHEET 4 OF 5 SAYS NO MECHANICAL VENTILATION. |
| | COORDINATE WITH ARCHITECT'S PLANS AND REVISE AS |
| | REQUIRED. |
| | |
| | 3- ARCHITECT TO REVISE ICYNENE INSULATION |
| | SPECIFICATIONS WALLS SECTIONS. ICYNENE IS AN OPEN CELL |
| | FOAM NOT CLOSED CELL. ALSO, COORDINATE WITH THE ENERGY |
| | CALCULATIONS AND THICKNESS REQUIRED TO MEET THE MINIMUM |
| | INSULATION REQUIRED BY TABLE 402.1.1. |
| | |
| | ***NOTE: PLEASE PROVIDE RESPONSE IN WRITING TO EXPEDITE |
| | THE REVIEW PROCESS. |
| | |