Plan Review Notes For Permit 12030455
Permit Number 12030455
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-19 17:08:25RESIDENTIAL (R3) RE-ROOF BUILDING REVIEW COMMENTS.
 2010 FLORIDA RESIDENTIAL CODE
  
 1- PLEASE SPECIFY WHICH APPROVED ASSEMBLY OF NOA
 09-0224.01 SUBMITTED IS GOING TO BE INSTALLED TO VERIFY
 COMPLIANCE WITH THE DESIGN PRESSURES OF SEC.
 R301.2.1.4.3.
 NOTE: ASSEMBLIES WITH GENERAL LIMITATION #9 CAN'T BE
 USED BECAUSE NAIL ENHANCING IS NOT ALLOWED.
  
 2- PLEASE PROVIDE SIGNED AND SEALED RAS 117
 CALCULATIONS FOR NAIL ENHANCING AT PERIMETER AND CORNER
 AREAS AS REQUIRED BY GENERAL LIMITATION #7 ON LAST PAGE
 OF NOA 09-0224.01 SUBMITTED.
 DESIGN PROFESSIONAL DOING THE CALCULATIONS TO TAKE INTO
 CONSIDERATION THAT THIS BUILDING IS LOCATED ON EXPOSURE
 "C". SEC. R301.2.1.4.3.
  
 3- PROVIDE RECORDED NOTICE OF COMMENCEMENT AS REQUIRED
 BY SEC. 713.13 FLORIDA STATUTES.
  
 4- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS. VALUATION WAS UPDATED
 PERMIT FEE BALANCE IS $139.03.
  
 IF YOU HAVE ANY QUESTIONS, PLEASE CALL
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712