| 2012-04-10 12:48:43 | 319 CLEMATIS STREET | | | PERMIT #12030454 | | | REVIEW COMMENTS - FIRE DEPARTMENT | | | | | | SHEET A2.0: INDICATE THE HOURLY FIRE RESISTANCE RATING | | | OF THE NEW FIRE RATED GLASS WALLS AND GLASS DOOR. DOOR | | | SHALL BE SELF CLOSING AND POSITIVE LATCHING. SUBMIT | | | PRODUCT DATA. | | | | | | EACH NEW SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE | | | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING | | | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS | | | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN | | | WIDTH. | | | | | | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO | | | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION | | | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL | | | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO | | | SMOKING" SIGNS POSTED. | | | | | | FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING | | | DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A | | | FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN | | | 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE | | | PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST | | | BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF | | | THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY. | | | | | | SEPARATE PLANS AND PERMITS ARE REQUIRED FOR THE | | | MODIFICATION OF THE FIRE SPRINKLER SYSTEM AND FIRE | | | ALARM SYSTEM. | | | | | | WESLEY JOLIN | | | OFFICE OF THE FIRE MARSHAL | | | WEST PALM BEACH FIRE RESCUE | | | |
|