| 2012-04-09 16:12:29 | BUILDING PLAN REVIEW |
| | PERMIT: 12030454 |
| | ADD: 319 CLEMATIS ST 1ST/ 2ND FLOOR COMMON AREAS |
| | CONT: CLAY KOHLMEYER GENERAL CONTRACTING |
| | TEL: (561)719-3429 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | 1) PLANS INDICATE THEY ARE DESIGNED TO THE 2007/09 FBC, |
| | AS OF MARCH 15, 2012 PLANS SUBMITTED FOR PERMIT ARE TO |
| | BE DESIGNED TO THE FAMILY OF 2010 FBCODES. |
| | |
| | 2) THE COVER SHEET & LIFE SAFETY SHEET INDICATE THIS |
| | BUILDING TO BE A TYPE II-B CONSTRUCTION. 2007/09 FBC-B |
| | TABLE 503 TO BE A 10 STORY BUILDING WITH BUSINESS |
| | OCCUPANCIES THE BUILDING TYPE WOULD BE A MINIMUM OF A |
| | TYPE IB. |
| | |
| | 3) THE PLANS ARE DEFICIENT IN INDICATING RATED WALLS, |
| | STAIRWELLS, FIRE PUMP ROOMS, TENANT SEPERATION WALLS, |
| | THERE ARE NO CUT SECTION OF WALLS INDICATING LISTED |
| | ASSEMBLIES AND HOUR OF FIRE RATING FOR FIRE RATED WALLS |
| | AND OPENING PROTECTIVES. FBC-B 707,708, 709 & TABLE |
| | 715.4. |
| | |
| | 4) PLEASE PROVIDE COMPLIANCE WITH 2010 FBC-B 713.6 |
| | "FIRE & SMOKE BARRIERS PROTECT ALL OPENINGS". |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |