Plan Review Notes For Permit 12030398
Permit Number 12030398
Review Stop M
Sequence Number 1
Notes
Date Text
2012-03-23 15:00:262007 FBC W/2009 REVISIONS
  
 MECHANICAL REVISION DENIED
  
 1) BALANCED RETURN AIR IS REQUIRED BY FBCR M1602.4. THE
 FIRST FLOOR GUEST BEDROOM AND THE SECOND FLOOR OFFICE
 REQUIRE RETURNS.
  
 2) AIR HANDLERS LOCATED IN ATTICS SHALL BE LOCATED
 WITHIN 6 FEET OF AN ACCESS OPENING AND COMPLY WITH FBCR
 M1305.1.3.
  