Plan Review Notes
Plan Review Notes For Permit 12030394
Permit Number 12030394
Review Stop M
Sequence Number 3
Notes
Date Text
2012-05-02 10:28:50PLAN DENIED
 1) MISSING FIRE DAMPER IN 34X18 DUCT AND 8" DUCT ON
 FIRST FLOOR.
 MISSING FIRE DAMPERS IN 36X18 DUCT AND 48X20 DUCT ON
 SECOND FLOOR.
 PER SECTION 607.5.1 2007 FBC (M)
 2) WHAT SECTION OF THE BUILDING DOES RTU # 3 COOL.
 3) ON SECOND FLOOR WHAT SIZE DUCT IS THE 36X16 AND
 48X20 TIEING IN TO.
 4) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS PER
 TABLE 403.3 FBC (M)
 5) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.2007
 FLORIDA ENERGY CODE.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]
  