Plan Review Notes
Plan Review Notes For Permit 12030394
Permit Number 12030394
Review Stop B
Sequence Number 3
Notes
Date Text
2012-05-01 12:07:01BUILDING PROVISO:
  
 1) SHEET A-1 & LS2 RED-LINED DRAWINGS FOR THE DOOR
 SCHEDULE, DOOR (F) TO BE A 4'-0" WIDE EGRESS DOOR. 2007
 FBC-B 1008.1.1 ALLOWS SIDE SWING EGRESS DOORS TO BE A
 MAXIMUM OF 48", NOT 4'-6". 46"/0.2= 230 OCCUPANT LOAD
 THROUGH THE DOOR, OCCUPANT LOAD FOR BOTH STAIRWELLS ARE
 LESS THAN THE 230.
  
 2) SHEET LS-1 REDLINED- ATRIUM WALL MISSING THE 1 HOUR
 FIRE RATING DESIGNATION WITHIN THE REVISION BUBBLE.
 2007 FBC-B 404.5.
  
 3) 2007 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE
 PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY
 OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE
 EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR
 STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY
 HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE
 ANY DECORATIVE CEILING AND IN CONCEALED SPACES.
 SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE
 AND SMOKE BARRIER - PROTECT ALL OPENINGS."
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  
 CONSTRUCTION SERVICES HOME PAGE
 HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP