| Plan Review Notes For Permit 12030394 |
| Permit Number |
12030394 |
|
| Review Stop |
B |
| Sequence Number |
3 |
|
| Notes |
| Date |
Text |
| 2012-05-01 12:07:01 | BUILDING PROVISO: | | | | | | 1) SHEET A-1 & LS2 RED-LINED DRAWINGS FOR THE DOOR | | | SCHEDULE, DOOR (F) TO BE A 4'-0" WIDE EGRESS DOOR. 2007 | | | FBC-B 1008.1.1 ALLOWS SIDE SWING EGRESS DOORS TO BE A | | | MAXIMUM OF 48", NOT 4'-6". 46"/0.2= 230 OCCUPANT LOAD | | | THROUGH THE DOOR, OCCUPANT LOAD FOR BOTH STAIRWELLS ARE | | | LESS THAN THE 230. | | | | | | 2) SHEET LS-1 REDLINED- ATRIUM WALL MISSING THE 1 HOUR | | | FIRE RATING DESIGNATION WITHIN THE REVISION BUBBLE. | | | 2007 FBC-B 404.5. | | | | | | 3) 2007 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE | | | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY | | | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE | | | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR | | | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY | | | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE | | | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. | | | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE | | | AND SMOKE BARRIER - PROTECT ALL OPENINGS." | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | CONSTRUCTION SERVICES HOME PAGE | | | HTTP://WWW.CITYOFWPB.COM/CONSTRUCTION/INDEX.PHP |
|