2012-04-18 13:10:02FBC 2007 PLUMBING REVIEW #2
 DENIED:
  
 1. SHEET A-1 SHOWS 8 SINGLE USER RESTROOMS. SHEET P-1
 SHOWS 5 SINGLE USER RESTROOMS.
  
 2. SHEETS A-1 & A-2 SHOW A TOTAL OF 7 SINKS THAT DO NOT
 APPEAR ON THE PLUMBING DRAWINGS.
  
 3. SHEET A-1 PLUMBING TABLE LISTS 18 DRINKING FOUNTAINS
 AND 2 SERVICE SINKS THAT DO NOT APPEAR ON A-1, A-2,
 P-1, OR P-2
  
 4. SHEET P-1 - 3 WATER CLOSETS AND 4 LAVS ARE MISSING
 IN THE GANG RESTROOMS ON EACH FLOOR.
  
 5. PLEASE SHOW THE LOCATION AND SIZE OF THE WATER
 HEATER/S.
 NOTE- 607.2 HOT WATER SUPPLY TEMPERATURE MAINTENANCE.
 WHERE THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE
 SOURCE OF HOT WATER SUPPLY TO THE FARTHEST FIXTURE
 EXCEEDS 100 FEET (30 480 MM), THE HOT WATER SUPPLY
 SYSTEM SHALL BE PROVIDED WITH A METHOD OF MAINTAINING
 THE TEMPERATURE IN ACCORDANCE WITH CHAPTER 13 OF THE
 FLORIDA BUILDING CODE, BUILDING .
 607.2.1 CIRCULATING SYSTEMS. PIPING INSULATION SHALL
 CONFORM TO THE REQUIREMENTS OF TABLE 607.1.
  