| Plan Review Notes For Permit 12030394 |
| Permit Number |
12030394 |
|
| Review Stop |
P |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-04-18 13:10:02 | FBC 2007 PLUMBING REVIEW #2 | | | DENIED: | | | | | | 1. SHEET A-1 SHOWS 8 SINGLE USER RESTROOMS. SHEET P-1 | | | SHOWS 5 SINGLE USER RESTROOMS. | | | | | | 2. SHEETS A-1 & A-2 SHOW A TOTAL OF 7 SINKS THAT DO NOT | | | APPEAR ON THE PLUMBING DRAWINGS. | | | | | | 3. SHEET A-1 PLUMBING TABLE LISTS 18 DRINKING FOUNTAINS | | | AND 2 SERVICE SINKS THAT DO NOT APPEAR ON A-1, A-2, | | | P-1, OR P-2 | | | | | | 4. SHEET P-1 - 3 WATER CLOSETS AND 4 LAVS ARE MISSING | | | IN THE GANG RESTROOMS ON EACH FLOOR. | | | | | | 5. PLEASE SHOW THE LOCATION AND SIZE OF THE WATER | | | HEATER/S. | | | NOTE- 607.2 HOT WATER SUPPLY TEMPERATURE MAINTENANCE. | | | WHERE THE DEVELOPED LENGTH OF HOT WATER PIPING FROM THE | | | SOURCE OF HOT WATER SUPPLY TO THE FARTHEST FIXTURE | | | EXCEEDS 100 FEET (30 480 MM), THE HOT WATER SUPPLY | | | SYSTEM SHALL BE PROVIDED WITH A METHOD OF MAINTAINING | | | THE TEMPERATURE IN ACCORDANCE WITH CHAPTER 13 OF THE | | | FLORIDA BUILDING CODE, BUILDING . | | | 607.2.1 CIRCULATING SYSTEMS. PIPING INSULATION SHALL | | | CONFORM TO THE REQUIREMENTS OF TABLE 607.1. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|