2012-04-16 09:58:29PLANS DENIED
 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC(M)
 .PAGE M101 A
 AND PAGE M120 A OF PLANS.
 2) INDICATE ON THE PLANS WHAT PART OF THE BUILDING RTU
 1,2,AND 3 COOL
 PER SECTION 106.3.4 SITE DRAWINGS.
 3) PAGE M601 OF THE PLANS SHOW TWO MINI SPLIT A/C UNITS
 INDICATE ON THE PLANS
 WHERE THEY ARE. PER SECTION 106.3.4 SITE DRAWINGS.
 4) REFER TO SECTION 13-409.AB.3.3 DAMPER SHUTOFF
 CONTROLS.
 2007 FLORIDA ENERGY CODE.