| Plan Review Notes For Permit 12030394 |
| Permit Number |
12030394 |
|
| Review Stop |
M |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-04-16 09:58:29 | PLANS DENIED | | | 1) REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC(M) | | | .PAGE M101 A | | | AND PAGE M120 A OF PLANS. | | | 2) INDICATE ON THE PLANS WHAT PART OF THE BUILDING RTU | | | 1,2,AND 3 COOL | | | PER SECTION 106.3.4 SITE DRAWINGS. | | | 3) PAGE M601 OF THE PLANS SHOW TWO MINI SPLIT A/C UNITS | | | INDICATE ON THE PLANS | | | WHERE THEY ARE. PER SECTION 106.3.4 SITE DRAWINGS. | | | 4) REFER TO SECTION 13-409.AB.3.3 DAMPER SHUTOFF | | | CONTROLS. | | | 2007 FLORIDA ENERGY CODE. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|