Plan Review Notes
Plan Review Notes For Permit 12030394
Permit Number 12030394
Review Stop B
Sequence Number 2
Notes
Date Text
2012-04-12 09:55:22BUILDING PLAN REVIEW
 PERMIT: 12030394
 ADD: 1889 PALM BEACH LAKES
 CONT: P & T CONSRUCTION, INC
 TEL: (561)324-8055
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 2ND REVIEW
 ACTION: DENIED
 APRIL 12/2012
  
 1) 2ND REQUEST, SHEET LS-1 & A-1 INDICATES THIS
 BUILDING AS A BUILDING TYPE IV PROTECTED, THIS
 NOMENCLATURE INDICATES THIS IS A CONSTRUCTED FROM HEAVY
 TIMBER. I BELIEVE THE DESIGNER IS USING
 BUILDING TYPES FROM THE 2001 FBC-B. THE 2001 FBC-B IV
 PROTECTED IS DEFINED UNDER THE 2007 FBC-B AS A TYPE IIA
 1 HOUR PROTECTED. THE PLANS ALSO INDICATE THIS
 STRUCTURE TO BE
 FULLY SPRINKLERED. PLEASE CORRECT TO THE 2007 FBC-B.
 THE DESIGNER DOES NOT STATE ON THIS SHEET TO WHICH CODE
 THE PLANS ARE DESIGNED. FIGURE 600 2007 FBC-B
 COMMENTARY.
  
 2) 2ND REQUEST, SEMI-COMPLIED. SEE ISST GRADE DOORS
 BACK TO BACK. 1028.3 DOORS THAT SWING INTO AN EXIT
 ACCESS CORRIDOR SHALL BE RECESSED TO PREVENT
 INTERFERENCE WITH CORRIDOR TRAFFIC; ANY DOORS NOT
 RECESSED SHALL OPEN 180 DEGREES (3.1 RAD) TO STOP
 AGAINST THE WALL. DOORS IN ANY POSITION SHALL NOT
 REDUCE THE REQUIRED CORRIDOR WIDTH BY MORE THAN
 ONE-HALF. NOTE NEITHER DOORS NOR CLASSROOMS ARE
 NUMBERED FOR IDENTIFYING PURPOSES, THESE CODE
 VIOLATIONS OCCUR BOTH IN THE DESIGN FIRST FLOOR AND
 SECOND FLOOR. MANY DOORS ARE CONFIGURERED IN THE CORNER
 OF CLASSROOMS BACK TO BACK SO THEY WOULD NOT BE ABLE TO
 SWING 180 DEGREES 6'-0" CORRIDORS WITH NO ALCOVES
 PROVIDED.
  
 3)2ND REQUEST. CHANGE OF OCCUPANCY, MIXED USE/ TO
 EDUCATIONAL 2007/09 EXISTING BLDG CODE 906.1
 ACCESSIBILITY. ACCESSIBILITY IN PORTIONS OF BUILDINGS
 UNDERGOING A CHANGE OF OCCUPANCY CLASSIFICATION SHALL
 COMPLY WITH CHAPTER 11 OF THE FLORIDA BUILDING CODE,
 BUILDING . 2007/09 FBC-B 11-4.1.3(5) PLEASE PROVIDE
 VERTICAL ACCESSIBILITY TO THE SECOND FLOOR. THE PLANS
 DO NOT INDICATE THE ELEVATOR OPENINGS, CURRENTLY IT
 APPEARS TO BE JUST A SHAFT.
  
 4) SEMI-COMPLIED. 1ST FLOOR PLEASE REVIEW ROOMS WITH
 660 SQ FT /33 TOTAL OCC LOAD, 2ND FLOOR ROOMS WITH 671
 SQ FT / 34 TOTAL OCC LOAD.
 DOOR SCHEDULE ON LS-2 INDICATES THE NEW ATRIUM DOORS AS
 EXISTING, NOT SHOWN ON THE EARLIER SET OF PLANS, PLEASE
 EXPLAIN THE COMMENT EXISTING?
 THE SECOND ISSUE WITH THE DOOR SCHEDULE ALL DOORS
 WITHIN THE DOOR SCHEDULE ARE INDICATED AS A 1INCH DOOR.
 PROVIDE DOCUMENTATION FOR ONE INCHE FIRE RATED DOORS.
 PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING EXITING,
 EXIT SIGNAGE, EMERGENCY LIGHTING OCCUPANT LOADS ROOMS,
 CORRIDORS, STAIRS & EXIT DOOR WAYS. ADMINISTATIVE CODE
 106.3.5.1.1
 THE CURRENT LS SHEET DOES NOT PROVIDE ENOUGH
 INFORMATION TO REVIEW FOR CODE COMPLIANCE.
 EXIST BLDG CODE 912.4.3 EGRESS CAPACITY. EGRESS
 CAPACITY SHALL MEET OR EXCEED THE OCCUPANT LOAD AS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING , FOR
 THE NEW OCCUPANCY.
 EXIST BLDG CODE. 805.2 MEANS OF EGRESS LIGHTING. MEANS
 OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR
 OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL
 LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 .
  
 EXIST BLDG CODE 805.3 EXIT SIGNS. MEANS OF EGRESS FROM
 THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT
 DISCHARGE SHALL BE PROVIDED WITH EXIT SIGNS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING .
  
 5) SEMI-COMPLIED. LIFE SAFETY SHEETS DO NOT INDICATE
 FIRE NOR SMOKE RATED WALLS. THE 1ST FLOOR AND 2ND FLOOR
 A SHEETS INDICATE THE ATRIUM WALLS AS 1 HOUR RATED,
 MECHANICAL ARE MISSING FIRE DAMPERS AND THE 1ST AND 2ND
 FLOOR CORRIDOR WALLS ARE INDICATED AS SMOKE PARTITIONS
 BUT ARE MISSING THE FIRE SMOKE DAMPERS. SEE 2007/09
 FBC-B SECTION 716.
  
 2007/09 EXISTING BUILDING CODE 902.1 (2) ATRIUMS.
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH
 THE FOLLOWING :
  
 2007/09 FBC-B 404.5 ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 706
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 EXCEPTIONS:
 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS
 SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE
 FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE
 GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 2. A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A 3/4-HOUR FIRE PROTECTION
 RATING.
 NOTE NONE OF THE CORRIDOR WALLS ARE INDICATED AS 1 HOUR
 RATED WALLS ALTHOUGH ALL OF THE DOORS INDICATE AS 1
 HOUR FIRE RATING.
 ----------------------
 NOTE!!!!! 2007/09 EXISTING BUILDING CODE 912.1.1
 COMPLIANCE WITH CHAPTER 8. ALSSO SEE 801.2 IN ADDITION
 TO THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6 &7.
  
 6)SEMI-COMPLIED SEE COMMENT # 5. PROVIDE INFORMATION
 FOR MONUMENTAL STAIR, IS IT PART OF THE REQUIRED MEANS
 OF EGRESS?
 2007 EXIST BLDG CODE 703.2.3 SUPPLEMENTAL STAIRWAY
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS SERVING THE WORK
 AREA SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA FLOOR AND ALL
 FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 2007/09 FBC-B 707.2 SHAFT ENCLOSURE NOT REQUIRED SEE
 EXCEPTION # 2. (DRAFT CURTAIN).
  
 7) 2ND REQUEST. PLEASE SEE EXIT ACCESS CORRIDOR THAT
 LEEDS PAST THE PANTRY THIS CORRIDOR SHOULD BE A MINIMUM
 OF 72" FBC-B 1017.2 EX # 4 .WITH OCCUPANT LOADS GREATER
 THAN 100 THIS CORRIDOR WILL NEED TO BE A MINIMUM OF 72"
 WIDE.
  
 8)2ND REQUEST. PLEASE SEE 2ND FLOOR PLAN THE CORRIDOR
 THAT LEEDS TO THE SIDE EXIT, IT APPEARS THE OCCUPANT
 LOAD FOR THE 2ND FLOOR IS OVER 100 REQUIRING THIS
 CORRIDOR TO BE 72 INCHES WIDE.
 FBC-B 1017.2 EX # 4.
  
 9)COMPLIED.
  
 10) 2ND REQUEST. EXIST BLDG CODE 912.2.1 PLEASE PROVIDE
 FIR SPRINKLER PLAN BASED ON THE NEW WALL CONFIGURATION
 & OCCUPANCY.WEST PALM BEACH ADMINISTRATIVE CODE
 106.3.5.1.1(5).
  
 11)2ND REQUEST. EIXST BLDG CODE 912.2.2 FIRE ALARM AND
 DETECTION SYSTEM. WHERE A CHANGE IN OCCUPANCY
 CLASSIFICATION OCCURS THAT REQUIRES A FIRE ALARM AND
 DETECTION SYSTEM TO BE PROVIDED BASED ON THE NEW
 OCCUPANCY IN ACCORDANCE WITH CHAPTER 9 OF THE FLORIDA
 BUILDING CODE, BUILDING , SUCH SYSTEM SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS. EXISTING ALARM NOTIFICATION APPLIANCES SHALL BE
 AUTOMATICALLY ACTIVATED THROUGHOUT THE BUILDING. WHERE
 THE BUILDING IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM,
 ALARM NOTIFICATION APPLIANCES SHALL BE PROVIDED
 THROUGHOUT THE AREA WHERE THE CHANGE OF OCCUPANCY
 OCCURS AND SHALL BE AUTOMATICALLY ACTIVATED.
  
 12) 2ND REQUEST. NOT SHOWN ON PLANS:
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 13) 2ND REQUEST. NOT SHOWN ON PLAN. 912.4.5 GUARDS.
 EXISTING GUARDS SHALL COMPLY WITH THE REQUIREMENTS IN
 SECTION 705.10 IN THE AREA OF THE CHANGE OF OCCUPANCY
 CLASSIFICATION.
  
 JAMES A. WITMER CBO