| 2012-03-26 15:32:44 | FBC PLUMBING 2007 REVIEW #1 |
| | DENIED: |
| | |
| | 1. NO TOTAL OCCUPANT LOAD WAS FOUND ON THE PLANS TO |
| | CALCULATE REQUIRED FIXTURES |
| | 403.1 MINIMUM NUMBER OF FIXTURES. |
| | EDUCATIONAL: |
| | WATER CLOSETS 1 PER 50 REQUIRED |
| | LAVATORIES 1 PER 50 REQUIRED |
| | DRINKING FOUNTAIN 1 PER 100 OCCUPANTS REQUIRED |
| | 1 SERVICE SINK REQUIRED |
| | |
| | 2. PLEASE INCLUDE THE FOLLOWING FOR REVIEW: |
| | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS. |
| | PLUMBING |
| | 1. MINIMUM PLUMBING FACILITIES |
| | 3. WATER SUPPLY PIPING |
| | 5. WATER HEATERS |
| | 6. VENTS |
| | 10. LOCATION OF WATER SUPPLY LINE |
| | 13. PLUMBING RISER (HOT AND COLD WATER) |
| | |
| | 3. A CLEANOUT IS REQUIRED AT THE BASE OF STACKS |
| | 708.3.4 BASE OF STACK. A CLEANOUT SHALL BE PROVIDED AT |
| | THE BASE OF EACH WASTE OR SOIL STACK. |
| | |
| | 4. THE FOLLOWING VENTS ARE MISSING FROM PLAN: |
| | THE CURCUIT VENTS BETWEEN THE 2 MOST UPSTREAM WATER |
| | CLOSETS IN THE WOMENS ROOMS. |
| | 911.2 VENT CONNECTION. |
| | |
| | THE COMMON VENT BETWEEN THE MENS WATER CLOSETS |
| | 908.1 INDIVIDUAL VENT AS COMMON VENT. |
| | |
| | THE VENTS FOR THE URINALS. |
| | 907.1 INDIVIDUAL VENT PERMITTED. |
| | |
| | 5. THE LAVS IN THE ADA STALLS APPEAR TO BE TOO CLOSE TO |
| | THE WATER CLOSET. PER FIGURE 30(E) THE LAV IS REQUIRED |
| | TO BE OUTSIDE OF THE 5' CLEAR SPACE OF THE WATER |
| | CLOSET. |
| | 11-4.17.3 SIZE AND ARRANGEMENT. |
| | THE STANDARD ACCESSIBLE RESTROOM STALL SHALL CONTAIN AN |
| | ACCESSIBLE LAVATORY WITHIN IT, THE SIZE OF SUCH |
| | LAVATORY TO BE NOT LESS THAN 19 INCHES WIDE BY 17 |
| | INCHES (483 MM BY 432 MM) DEEP, NOMINAL SIZE, AND WALL |
| | MOUNTED. THE LAVATORY SHALL BE MOUNTED SO AS NOT TO |
| | OVERLAP THE CLEAR FLOOR SPACE AREAS REQUIRED BY SECTION |
| | 11-4.17 [SEE FIGURE 30(A) AND FIGURE 30(E)] AND TO |
| | COMPLY WITH SECTION 11-4.19 OF THE CODE. SUCH |
| | LAVATORIES SHALL BE COUNTED AS PART OF THE REQUIRED |
| | FIXTURE COUNT FOR THE BUILDING. |
| | |
| | REVIEW BY |
| | LARRY WAGNER |
| | CHIEF PLUMBING INSPECTOR |
| | PHONE # 805-6692 |
| | EMAIL [email protected] |
| | FAX # 805-6676 |
| | |
| | |
| | |
| | |
| | |
| | |