| Plan Review Notes For Permit 12030394 |
| Permit Number |
12030394 |
|
| Review Stop |
E |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-19 10:05:12 | 12030394 | | | 1889 PALM BEACH LAKES BLVD | | | NEW EDUCATIONAL FACILITY | | | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE. NEC 110.9 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | | NEC 110.26, 240.24, 408.17 | | | SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL | | | SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE | | | NEW ELECTRICAL CIRCUITS. NEC 210.3 | | | SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE EXISTING | | | SERVICE RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC | | | 230.24, 230.72 | | | SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC | | | 250.20 | | | VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND | | | GROUPED IN ONE LOCATION. NEC 230.2, 230.71 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31 | | | A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A | | | SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS | | | REQUIRED. NFPA 101 15.3.4, FBC 907 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|