2012-03-19 10:05:1212030394
 1889 PALM BEACH LAKES BLVD
 NEW EDUCATIONAL FACILITY
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL
 SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE
 NEW ELECTRICAL CIRCUITS. NEC 210.3
 SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE EXISTING
 SERVICE RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC
 230.24, 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC
 250.20
 VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND
 GROUPED IN ONE LOCATION. NEC 230.2, 230.71
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
 A FIRE ALARM SYSTEM IS REQUIRED FOR THIS FACILITY. A
 SEPARATE PERMIT WITH PLAN AND SHOP DRAWINGS IS
 REQUIRED. NFPA 101 15.3.4, FBC 907
  