Plan Review Notes
Plan Review Notes For Permit 12030394
Permit Number 12030394
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-22 09:50:34BUILDING PLAN REVIEW
 PERMIT: 12030394
 ADD: 1889 PALM BEACH LAKES
 CONT: P & T CONSRUCTION, INC
 TEL: (561)324-8055
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH AMENDMENTS
  
 2007 EXISTING BUILDING CODE LEVEL II 701.3
 COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS,
 SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS
 OF THE FLORIDA BUILDING CODE, BUILDING.
  
 1ST REVIEW
 ACTION: DENIED
  
 1) SHEET SP-1 & A-1 INDICATES THIS BUILDING AS A
 BUILDING TYPE IV PROTECTED, THIS NOMENCLATURE INDICATES
 THIS IS A CONSTRUCTED FROM HEAVY TIMBER. I BELIEVE THE
 DESIGNER IS USING
 BUILDING TYPES FROM THE 2001 FBC-B. THE 2001 FBC-B IV
 PROTECTED IS DEFINED UNDER THE 2007 FBC-B AS A TYPE IIA
 1 HOUR PROTECTED. THE PLANS ALSO INDICATE THIS
 STRUCTURE TO BE
 FULLY SPRINKLERED. PLEASE CORRECT TO THE 2007 FBC-B.
 THE DESIGNER DOES NOT STATE ON THIS SHEET TO WHICH CODE
 THE PLANS ARE DESIGNED. FIGURE 600 2007 FBC-B
 COMMENTARY.
  
 2) 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR
 SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR
 TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES
 (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY
 POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH
 BY MORE THAN ONE-HALF. NOTE NEITHER DOORS NOR
 CLASSROOMS ARE NUMBERED FOR IDENTIFYING PURPOSES, THESE
 CODE VIOLATIONS OCCUR BOTH IN THE DESIGN FIRST FLOOR
 AND SECOND FLOOR. MANY DOORS ARE CONFIGURERED IN THE
 CORNER OF CLASSROOMS BACK TO BACK SO THEY WOULD NOT BE
 ABLE TO SWING 180 DEGREES 6'-0" CORRIDORS WITH NO
 ALCOVES PROVIDED.
  
 3) CHANGE OF OCCUPANCY, MIXED USE/ TO EDUCATIONAL
 2007/09 EXISTING BLDG CODE 906.1 ACCESSIBILITY.
 ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A
 CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH
 CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING .
 2007/09 FBC-B 11-4.1.3(5) PLEASE PROVIDE VERTICAL
 ACCESSIBILITY TO THE SECOND FLOOR. THE PLANS DO NOT
 INDICATE THE ELEVATOR OPENINGS, CURRENTLY IT APPEARS TO
 BE JUST A SHAFT.
  
 4) PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING EXITING,
 EXIT SIGNAGE, EMERGENCY LIGHTING OCCUPANT LOADS ROOMS,
 CORRIDORS, STAIRS & EXIT DOOR WAYS. ADMINISTATIVE CODE
 106.3.5.1.1
 THE CURRENT LS SHEET DOES NOT PROVIDE ENOUGH
 INFORMATION TO REVIEW FOR CODE COMPLIANCE.
 EXIST BLDG CODE 912.4.3 EGRESS CAPACITY. EGRESS
 CAPACITY SHALL MEET OR EXCEED THE OCCUPANT LOAD AS
 SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING , FOR
 THE NEW OCCUPANCY.
 EXIST BLDG CODE. 805.2 MEANS OF EGRESS LIGHTING. MEANS
 OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR
 OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL
 LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE WITH
 THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING
 .
  
 EXIST BLDG CODE 805.3 EXIT SIGNS. MEANS OF EGRESS FROM
 THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT
 DISCHARGE SHALL BE PROVIDED WITH EXIT SIGNS IN
 ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA
 BUILDING CODE, BUILDING .
  
 5) 2007/09 EXISTING BUILDING CODE 902.1 (2) ATRIUMS.
 PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH
 THE FOLLOWING :
  
 2007/09 FBC-B 404.5 ENCLOSURE OF ATRIUMS. ATRIUM SPACES
 SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR
 FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 706
 OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH
 SECTION 711, OR BOTH.
 EXCEPTIONS:
 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE
 AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR
 LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE
 ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM
 SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND
 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE
 ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF
 THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS
 SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE
 FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE
 GLASS BEFORE THE SPRINKLER SYSTEM OPERATES.
 2. A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH
 SECTION 2110 AND HAVING A 3/4-HOUR FIRE PROTECTION
 RATING.
 NOTE NONE OF THE CORRIDOR WALLS ARE INDICATED AS 1 HOUR
 RATED WALLS ALTHOUGH ALL OF THE DOORS INDICATE AS 1
 HOUR FIRE RATING.
 ----------------------
 NOTE!!!!! 2007/09 EXISTING BUILDING CODE 912.1.1
 COMPLIANCE WITH CHAPTER 8. ALSSO SEE 801.2 IN ADDITION
 TO THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY
 WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6 &7.
  
 6) PROVIDE INFORMATION FOR MONUMENTAL STAIR, IS IT PART
 OF THE REQUIRED MEANS OF EGRESS?
 2007 EXIST BLDG CODE 703.2.3 SUPPLEMENTAL STAIRWAY
 ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY
 FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS
 THAT ARE PART OF THE MEANS OF EGRESS SERVING THE WORK
 AREA SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT
 CONSTRUCTION ON THE HIGHEST WORK AREA FLOOR AND ALL
 FLOORS BELOW.
 EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY
 THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE
 PREVENTION CODE.
 2007/09 FBC-B 707.2 SHAFT ENCLOSURE NOT REQUIRED SEE
 EXCEPTION # 2. (DRAFT CURTAIN).
  
 7) PLEASE SEE EXIT ACCESS CORRIDOR THAT LEEDS PAST THE
 PANTRY THIS CORRIDOR SHOULD BE A MINIMUM OF 72" FBC-B
 1017.2 EX # 4.
  
 8) PLEASE SEE 2ND FLOOR PLAN THE CORRIDOR THAT LEEDS TO
 THE SIDE EXIT, IT APPEARS THE OCCUPANT LOAD FOR THE 2ND
 FLOOR IS OVER 100 REQUIRING THIS CORRIDOR TO BE 72
 INCHES WIDE.
 FBC-B 1017.2 EX # 4.
  
 9) 2ND FLOOR PLAN, DOORS THAT DO NOT HAVE THE 18"
 CLEARANCE ON THE LATCH SIDE OF THE DOOR, FBC-B
 11-4.13.6. SEE DOOR NEAR GRID LINE E-4, STAFF ROOM AND
 CLASSROOM LOCATED NEAR GRID LINE 12 HALF WAY BETWEEN A
 & B.
  
 10) EXIST BLDG CODE 912.2.1 PLEASE PROVIDE FIR
 SPRINKLER PLAN BASED ON THE NEW WALL CONFIGURATION &
 OCCUPANCY.
  
 11) EIXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION
 SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION
 OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM
 TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE
 WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING ,
 SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE
 THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM
 NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY
 ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING
 IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM
 NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT
 THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL
 BE AUTOMATICALLY ACTIVATED.
  
 12) NOT SHOWN ON PLANS:
 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH
 THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA
 OF THE CHANGE OF OCCUPANCY CLASSIFICATION.
  
 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE
 REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE
 CHANGE OF OCCUPANCY CLASSIFICATION.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676