| 2012-03-22 09:50:34 | BUILDING PLAN REVIEW |
| | PERMIT: 12030394 |
| | ADD: 1889 PALM BEACH LAKES |
| | CONT: P & T CONSRUCTION, INC |
| | TEL: (561)324-8055 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) SHEET SP-1 & A-1 INDICATES THIS BUILDING AS A |
| | BUILDING TYPE IV PROTECTED, THIS NOMENCLATURE INDICATES |
| | THIS IS A CONSTRUCTED FROM HEAVY TIMBER. I BELIEVE THE |
| | DESIGNER IS USING |
| | BUILDING TYPES FROM THE 2001 FBC-B. THE 2001 FBC-B IV |
| | PROTECTED IS DEFINED UNDER THE 2007 FBC-B AS A TYPE IIA |
| | 1 HOUR PROTECTED. THE PLANS ALSO INDICATE THIS |
| | STRUCTURE TO BE |
| | FULLY SPRINKLERED. PLEASE CORRECT TO THE 2007 FBC-B. |
| | THE DESIGNER DOES NOT STATE ON THIS SHEET TO WHICH CODE |
| | THE PLANS ARE DESIGNED. FIGURE 600 2007 FBC-B |
| | COMMENTARY. |
| | |
| | 2) 1028.3 DOORS THAT SWING INTO AN EXIT ACCESS CORRIDOR |
| | SHALL BE RECESSED TO PREVENT INTERFERENCE WITH CORRIDOR |
| | TRAFFIC; ANY DOORS NOT RECESSED SHALL OPEN 180 DEGREES |
| | (3.1 RAD) TO STOP AGAINST THE WALL. DOORS IN ANY |
| | POSITION SHALL NOT REDUCE THE REQUIRED CORRIDOR WIDTH |
| | BY MORE THAN ONE-HALF. NOTE NEITHER DOORS NOR |
| | CLASSROOMS ARE NUMBERED FOR IDENTIFYING PURPOSES, THESE |
| | CODE VIOLATIONS OCCUR BOTH IN THE DESIGN FIRST FLOOR |
| | AND SECOND FLOOR. MANY DOORS ARE CONFIGURERED IN THE |
| | CORNER OF CLASSROOMS BACK TO BACK SO THEY WOULD NOT BE |
| | ABLE TO SWING 180 DEGREES 6'-0" CORRIDORS WITH NO |
| | ALCOVES PROVIDED. |
| | |
| | 3) CHANGE OF OCCUPANCY, MIXED USE/ TO EDUCATIONAL |
| | 2007/09 EXISTING BLDG CODE 906.1 ACCESSIBILITY. |
| | ACCESSIBILITY IN PORTIONS OF BUILDINGS UNDERGOING A |
| | CHANGE OF OCCUPANCY CLASSIFICATION SHALL COMPLY WITH |
| | CHAPTER 11 OF THE FLORIDA BUILDING CODE, BUILDING . |
| | 2007/09 FBC-B 11-4.1.3(5) PLEASE PROVIDE VERTICAL |
| | ACCESSIBILITY TO THE SECOND FLOOR. THE PLANS DO NOT |
| | INDICATE THE ELEVATOR OPENINGS, CURRENTLY IT APPEARS TO |
| | BE JUST A SHAFT. |
| | |
| | 4) PLEASE PROVIDE A LIFE SAFETY PLAN PROVIDING EXITING, |
| | EXIT SIGNAGE, EMERGENCY LIGHTING OCCUPANT LOADS ROOMS, |
| | CORRIDORS, STAIRS & EXIT DOOR WAYS. ADMINISTATIVE CODE |
| | 106.3.5.1.1 |
| | THE CURRENT LS SHEET DOES NOT PROVIDE ENOUGH |
| | INFORMATION TO REVIEW FOR CODE COMPLIANCE. |
| | EXIST BLDG CODE 912.4.3 EGRESS CAPACITY. EGRESS |
| | CAPACITY SHALL MEET OR EXCEED THE OCCUPANT LOAD AS |
| | SPECIFIED IN THE FLORIDA BUILDING CODE, BUILDING , FOR |
| | THE NEW OCCUPANCY. |
| | EXIST BLDG CODE. 805.2 MEANS OF EGRESS LIGHTING. MEANS |
| | OF EGRESS FROM THE HIGHEST WORK AREA FLOOR TO THE FLOOR |
| | OF EXIT DISCHARGE SHALL BE PROVIDED WITH ARTIFICIAL |
| | LIGHTING WITHIN THE EXIT ENCLOSURE IN ACCORDANCE WITH |
| | THE REQUIREMENTS OF THE FLORIDA BUILDING CODE, BUILDING |
| | . |
| | |
| | EXIST BLDG CODE 805.3 EXIT SIGNS. MEANS OF EGRESS FROM |
| | THE HIGHEST WORK AREA FLOOR TO THE FLOOR OF EXIT |
| | DISCHARGE SHALL BE PROVIDED WITH EXIT SIGNS IN |
| | ACCORDANCE WITH THE REQUIREMENTS OF THE FLORIDA |
| | BUILDING CODE, BUILDING . |
| | |
| | 5) 2007/09 EXISTING BUILDING CODE 902.1 (2) ATRIUMS. |
| | PLEASE PROVIDE DOCUMENTATION FOR CODE COMPLIANCE WITH |
| | THE FOLLOWING : |
| | |
| | 2007/09 FBC-B 404.5 ENCLOSURE OF ATRIUMS. ATRIUM SPACES |
| | SHALL BE SEPARATED FROM ADJACENT SPACES BY A 1-HOUR |
| | FIRE BARRIER CONSTRUCTED IN ACCORDANCE WITH SECTION 706 |
| | OR A HORIZONTAL ASSEMBLY CONSTRUCTED IN ACCORDANCE WITH |
| | SECTION 711, OR BOTH. |
| | EXCEPTIONS: |
| | 1. A GLASS WALL FORMING A SMOKE PARTITION WHERE |
| | AUTOMATIC SPRINKLERS ARE SPACED 6 FEET (1829 MM) OR |
| | LESS ALONG BOTH SIDES OF THE SEPARATION WALL, OR ON THE |
| | ROOM SIDE ONLY IF THERE IS NOT A WALKWAY ON THE ATRIUM |
| | SIDE, AND BETWEEN 4 INCHES AND 12 INCHES (102 MM AND |
| | 305 MM) AWAY FROM THE GLASS AND DESIGNED SO THAT THE |
| | ENTIRE SURFACE OF THE GLASS IS WET UPON ACTIVATION OF |
| | THE SPRINKLER SYSTEM WITHOUT OBSTRUCTION. THE GLASS |
| | SHALL BE INSTALLED IN A GASKETED FRAME SO THAT THE |
| | FRAMING SYSTEM DEFLECTS WITHOUT BREAKING (LOADING) THE |
| | GLASS BEFORE THE SPRINKLER SYSTEM OPERATES. |
| | 2. A GLASS-BLOCK WALL ASSEMBLY IN ACCORDANCE WITH |
| | SECTION 2110 AND HAVING A 3/4-HOUR FIRE PROTECTION |
| | RATING. |
| | NOTE NONE OF THE CORRIDOR WALLS ARE INDICATED AS 1 HOUR |
| | RATED WALLS ALTHOUGH ALL OF THE DOORS INDICATE AS 1 |
| | HOUR FIRE RATING. |
| | ---------------------- |
| | NOTE!!!!! 2007/09 EXISTING BUILDING CODE 912.1.1 |
| | COMPLIANCE WITH CHAPTER 8. ALSSO SEE 801.2 IN ADDITION |
| | TO THE PROVISIONS OF THIS CHAPTER, WORK SHALL COMPLY |
| | WITH ALL OF THE REQUIREMENTS OF CHAPTERS 6 &7. |
| | |
| | 6) PROVIDE INFORMATION FOR MONUMENTAL STAIR, IS IT PART |
| | OF THE REQUIRED MEANS OF EGRESS? |
| | 2007 EXIST BLDG CODE 703.2.3 SUPPLEMENTAL STAIRWAY |
| | ENCLOSURE REQUIREMENTS. WHERE THE WORK AREA ON ANY |
| | FLOOR EXCEEDS 50 PERCENT OF THAT FLOOR AREA, STAIRWAYS |
| | THAT ARE PART OF THE MEANS OF EGRESS SERVING THE WORK |
| | AREA SHALL, AT A MINIMUM, BE ENCLOSED WITH SMOKE-TIGHT |
| | CONSTRUCTION ON THE HIGHEST WORK AREA FLOOR AND ALL |
| | FLOORS BELOW. |
| | EXCEPTION: WHERE STAIRWAY ENCLOSURE IS NOT REQUIRED BY |
| | THE FLORIDA BUILDING CODE OR THE FLORIDA FIRE |
| | PREVENTION CODE. |
| | 2007/09 FBC-B 707.2 SHAFT ENCLOSURE NOT REQUIRED SEE |
| | EXCEPTION # 2. (DRAFT CURTAIN). |
| | |
| | 7) PLEASE SEE EXIT ACCESS CORRIDOR THAT LEEDS PAST THE |
| | PANTRY THIS CORRIDOR SHOULD BE A MINIMUM OF 72" FBC-B |
| | 1017.2 EX # 4. |
| | |
| | 8) PLEASE SEE 2ND FLOOR PLAN THE CORRIDOR THAT LEEDS TO |
| | THE SIDE EXIT, IT APPEARS THE OCCUPANT LOAD FOR THE 2ND |
| | FLOOR IS OVER 100 REQUIRING THIS CORRIDOR TO BE 72 |
| | INCHES WIDE. |
| | FBC-B 1017.2 EX # 4. |
| | |
| | 9) 2ND FLOOR PLAN, DOORS THAT DO NOT HAVE THE 18" |
| | CLEARANCE ON THE LATCH SIDE OF THE DOOR, FBC-B |
| | 11-4.13.6. SEE DOOR NEAR GRID LINE E-4, STAFF ROOM AND |
| | CLASSROOM LOCATED NEAR GRID LINE 12 HALF WAY BETWEEN A |
| | & B. |
| | |
| | 10) EXIST BLDG CODE 912.2.1 PLEASE PROVIDE FIR |
| | SPRINKLER PLAN BASED ON THE NEW WALL CONFIGURATION & |
| | OCCUPANCY. |
| | |
| | 11) EIXST BLDG CODE 912.2.2 FIRE ALARM AND DETECTION |
| | SYSTEM. WHERE A CHANGE IN OCCUPANCY CLASSIFICATION |
| | OCCURS THAT REQUIRES A FIRE ALARM AND DETECTION SYSTEM |
| | TO BE PROVIDED BASED ON THE NEW OCCUPANCY IN ACCORDANCE |
| | WITH CHAPTER 9 OF THE FLORIDA BUILDING CODE, BUILDING , |
| | SUCH SYSTEM SHALL BE PROVIDED THROUGHOUT THE AREA WHERE |
| | THE CHANGE OF OCCUPANCY OCCURS. EXISTING ALARM |
| | NOTIFICATION APPLIANCES SHALL BE AUTOMATICALLY |
| | ACTIVATED THROUGHOUT THE BUILDING. WHERE THE BUILDING |
| | IS NOT EQUIPPED WITH A FIRE ALARM SYSTEM, ALARM |
| | NOTIFICATION APPLIANCES SHALL BE PROVIDED THROUGHOUT |
| | THE AREA WHERE THE CHANGE OF OCCUPANCY OCCURS AND SHALL |
| | BE AUTOMATICALLY ACTIVATED. |
| | |
| | 12) NOT SHOWN ON PLANS: |
| | 912.4.4 HANDRAILS. EXISTING STAIRWAYS SHALL COMPLY WITH |
| | THE HANDRAIL REQUIREMENTS OF SECTION 705.9 IN THE AREA |
| | OF THE CHANGE OF OCCUPANCY CLASSIFICATION. |
| | |
| | 912.4.5 GUARDS. EXISTING GUARDS SHALL COMPLY WITH THE |
| | REQUIREMENTS IN SECTION 705.10 IN THE AREA OF THE |
| | CHANGE OF OCCUPANCY CLASSIFICATION. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |