| Plan Review Notes For Permit 12030390 |
| Permit Number |
12030390 |
|
| Review Stop |
P |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-27 14:10:56 | FBC PLUMBING 2007 REVIEW #1 | | | DENIED: | | | | | | 1. SHEET 5.1 SHOWS WHAT APPEARS TO BE OFFICE SPACE WITH | | | A RESIDENTIAL BATHROOM AND KITCHEN. IF THIS SPACE IS | | | BUSINESS, COMPLIANCE WITH THE ACCESSIBILITY CODE WILL | | | BE REQUIRED AND A DRINKING FOUNTAIN WILL BE REQUIRED | | | PER 403.1 MINIMUM NUMBER OF REQUIRED FIXTURES. | | | IF THE SPACE IS R-3 - AN AUTOMATIC CLOTHES WASHER | | | CONNECTION WILL BE REQUIRED. | | | | | | 2. PLEASE INCLUDE THE FOLLOWING ON THE DRAWINGS. | | | 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS: | | | PLUMBING | | | 1. MINIMUM PLUMBING FACILITIES | | | 3. WATER SUPPLY PIPING | | | 5. WATER HEATERS | | | 8. BACK FLOW PREVENTION | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | | | | | | | |
|