| 2012-03-19 12:37:57 | 12030390 | | | 209 S. OLIVE AVE. | | | R-3 WITH STORAGE RESIDENTIAL UNIT | | | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE. NEC 110.9 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | VERIFY THE ELECTRICAL SERVICE MAINS ARE SIX OR LESS AND | | | GROUPED IN ONE LOCATION. THE SITE PLANS SUGGEST THIS | | | BUILDING MAY BE ALREADY SERVED FROM ANOTHER LOCATION. | | | NEC 230.2, 230.71 | | | REMODELING OF AN EXISTING STRUCTURE IS REQUIRED TO | | | INCLUDE INTERCONNECTED SMOKE DETECTORS IF THEY DO NOT | | | ALREADY EXIST WITHIN THE RESIDENCE. IF THE RESIDENCE | | | HAS GAS APPLIANCES, AN ATTACHED GARAGE OR A FIRE PLACE | | | A CARBON MONOXIDE DETECTOR IS REQUIRED WITHIN TEN FEET | | | OF EACH ROOM USED FOR SLEEPING. FBC R313 | | | ALL NEW RECEPTACLES SHALL BE TAMPER RESISTANT. 2008 NEC | | | 406.11 | | | GFCI PROTECTION REQUIRED FOR RECEPTACLES IN THE GARAGE. | | | NEC 210.8 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | |
|