Plan Review Notes
Plan Review Notes For Permit 12030383
Permit Number 12030383
Review Stop E
Sequence Number 2
Notes
Date Text
2012-04-30 14:27:4912030383
 1101 CHARLES ST.
 GROUP A3
 SANCTUARY BUILDING
  
 PLEASE NOTE THE FOLLOWING ITEMS STILL REQUIRE A
 RESPONSE:
  
 VERIFY THAT ALL NEW ELECTRICAL EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING
 CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN
 PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS.
 NEC 110.26, 240.24, 408.17
 SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL
 SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE
 NEW ELECTRICAL CIRCUITS. NEC 210.3
 SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE SERVICE
 RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC 230.24,
 230.72
 SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC
 250.20
 PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94
 PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31
 GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC WATER
 COOLER. NEC 422.52
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS
 13-415.ABC.1.3
  