| Date |
Text |
| 2012-04-30 14:27:49 | 12030383 |
| | 1101 CHARLES ST. |
| | GROUP A3 |
| | SANCTUARY BUILDING |
| | |
| | PLEASE NOTE THE FOLLOWING ITEMS STILL REQUIRE A |
| | RESPONSE: |
| | |
| | VERIFY THAT ALL NEW ELECTRICAL EQUIPMENT INTENDED TO |
| | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING |
| | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND |
| | CURRENT THAT IS AVAILABLE. NEC 110.9 |
| | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING |
| | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN |
| | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. |
| | NEC 110.26, 240.24, 408.17 |
| | SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL |
| | SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE |
| | NEW ELECTRICAL CIRCUITS. NEC 210.3 |
| | SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE SERVICE |
| | RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC 230.24, |
| | 230.72 |
| | SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC |
| | 250.20 |
| | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 |
| | PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31 |
| | GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC WATER |
| | COOLER. NEC 422.52 |
| | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING |
| | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE |
| | REQUIREMENTS. FBC 13-415 ABC.5 |
| | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE |
| | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. |
| | SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS |
| | 13-415.ABC.1.3 |
| | |
| | ROBERT LECKY |
| | ELECTRIC PLANS EXAMINER |
| | [email protected] |
| | 561-805-6718 |
| | |
| | |