| Plan Review Notes For Permit 12030383 |
| Permit Number |
12030383 |
|
| Review Stop |
M |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-04-17 11:11:01 | PLANS DENIED | | | 1) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS 106.3.5.1.4 | | | MECHANICAL. | | | 2) PROVIDE BATHROOM EXHAUST ON THE PLANS. PER TABLE | | | 403.3 2010 FBC (M) | | | 3) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS 403.3 | | | 2010 FBC (M) | | | 4) PROVIDE ENERGY CALCULATION WITH THE PLANS PER | | | 503.2.1 | | | CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY | | | CODE | | | 5) PLEASE PROVIDE A COMPLETE SET OF MECHANICAL PLANS. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|