Plan Review Notes
Plan Review Notes For Permit 12030383
Permit Number 12030383
Review Stop M
Sequence Number 1
Notes
Date Text
2012-04-17 11:11:01PLANS DENIED
 1) PROVIDE EQUIPMENT SCHEDULE ON THE PLANS 106.3.5.1.4
 MECHANICAL.
 2) PROVIDE BATHROOM EXHAUST ON THE PLANS. PER TABLE
 403.3 2010 FBC (M)
 3) PROVIDE FRESH AIR CALCULATIONS ON THE PLANS 403.3
 2010 FBC (M)
 4) PROVIDE ENERGY CALCULATION WITH THE PLANS PER
 503.2.1
 CALCULATION OF HEATING AND COOLING 2010 FLORIDA ENERGY
 CODE
 5) PLEASE PROVIDE A COMPLETE SET OF MECHANICAL PLANS.
 PLAN REVIEW BY HAROLD MOSER
 561-805-6732
 [email protected]