| Date |
Text |
| 2012-04-19 09:46:50 | 1101 CHARLES STREET |
| | PERMIT #12030383 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | THE EXISTING BUILDING IS ADDRESSED AS 1101 CHARLES |
| | STREET, PLEASE INDICATE THE ADDRESS OF THE NEW |
| | SANCTUARY BUILDING. |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | PORTABLE FIRE EXTINGUISHERS SHALL HAVE A MINIMUM RATING |
| | OF 2A:10BC AND SHALL BE TAGGED BY A LICENSED FIRE |
| | EXTINGUISHER COMPANY. |
| | |
| | PROVIDE BUILDING ADDRESS VISIBLE FROM THE STREET. |
| | NUMBERS SHALL BE ATTACHED TO THE BUILDING AND BE AT |
| | LEAST SIX-INCHES IN HEIGHT WITH 1-INCH STROKE AND SHALL |
| | CONTRAST THE BACKGROUND. |
| | |
| | STRUCTURES WITH LIGHT FRAME FLOOR/ROOF TRUSS |
| | CONSTRUCTION SHALL BE IDENTIFIED WITH A SIGN AFFIXED TO |
| | THE BUILDING. THE SIGN SHALL FEATURE A MALTESE CROSS |
| | 8-INCHES WIDE AND 8-INCHES TALL AND BE OF A BRIGHT RED |
| | REFLECTIVE COLOR AND BEAR THE LETTER "R" DESIGNATION |
| | PER FLORIDA STATUTE 633.027 AND FLORIDA ADMINISTRATIVE |
| | CODE 69A-60.0081. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | PROVIDE STAIR AND HANDRAIL DETAILS FOR THE ACCESSIBLE |
| | RAMP AND THE STAGE STEPS. |
| | |
| | SHEET A1.01: DOOR D7 NEEDS TO BE EQUIPPED WITH PANIC |
| | HARDWARE. |
| | |
| | SHEET LS1.01: STUDY ROOM #201 IS INDICATED AS AN EXIT |
| | FROM THE SANCTUARY; HOWEVER, THERE ARE NOT EXIT SIGNS |
| | IN THE SANCTUARY MAKING THIS EXIT OBVIOUS. DOOR FRAME |
| | WIDTH INTO THE STUDY ROOM #201 IS 20-INCHES. |
| | |
| | ELECTRICAL DRAWINGS DO NOT SHOW POWER TO EXIT SIGNS, |
| | EMERGENCY LIGHTING OR SMOKE DETECTORS. |
| | |
| | INTERIOR WALL AND CEILING FINISHES IN THE FOYER SHALL |
| | BE CLASS A OR B. CLASS C FINISHES ARE ACCETABLE IN |
| | OTHER AREAS. |
| | |
| | CURTAINS, DRAPES AND OTHER LOOSELY HANGING |
| | FINISHINGS/DECORATIONS SHALL MEET THE FLAME PROPAGATION |
| | CRITERIA OF NFPA 701 (MATERIAL WILL SELF EXTINGUISH |
| | ONCE DIRECT FIRE FLAME HAS BEEN REMOVED). |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |