| 2012-03-19 14:44:36 | 12030383 | | | 1101 CHARLES ST. | | | GROUP A3 | | | SANCTUARY BUILDING | | | | | | VERIFY THAT ALL NEW ELECTRICAL EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE. NEC 110.9 | | | PROVIDE A DETAIL SHOWING THAT THE REQUIRED WORKING | | | CLEARANCES AND DEDICATED WORKING SPACE HAS BEEN | | | PROVIDED FOR THE ELECTRICAL EQUIPMENT AND PANEL BOARDS. | | | NEC 110.26, 240.24, 408.17 | | | SHOW LOCATION OF ALL PANEL BOARDS. PROVIDE PANEL | | | SCHEDULE SHOWING RATING, SIZE AND WIRING METHOD FOR THE | | | NEW ELECTRICAL CIRCUITS. NEC 210.3 | | | SHOW SERVICE LOCATION ON THE PLAN. VERIFY THE SERVICE | | | RISER HAS ADEQUATE SIZE AND CLEARANCE. NEC 230.24, | | | 230.72 | | | SHOW ALL SERVICE GROUNDING AND BONDING. NEC 215.5, NEC | | | 250.20 | | | PROVIDE AN INTERSYSTEM BONDING POINT. NEC 250.94 | | | PROVIDE A SUMMARY LOAD CALCULATION. NEC 230.31 | | | GFCI PROTECTION IS REQUIRED FOR THE ELECTRIC WATER | | | COOLER. NEC 422.52 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | SPECIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | | SPACE CONTROL FBC 13-415 ABC.1.2.; ADDITIONAL CONTROLS | | | 13-415.ABC.1.3 | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|