Plan Review Notes
Plan Review Notes For Permit 12030383
Permit Number 12030383
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-25 10:59:21 
 BUILDING PLAN REVIEW
 PERMIT: 12030383
 ADD: 1101 CHARLES ST
 CONT: CANCIO BUILDERS, INC
 TEL: (772)263-0169
  
 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS
 * WEST PALM BEACH ADMINISTRATIVE AMENDMENTS
  
 1 ST REVIEW
 ACTION: DENIED
  
 1) 106.3.5 MINIMUM PLAN REVIEW CRITERIA FOR BUILDINGS.
 THE EXAMINATION OF THE DOCUMENTS BY THE BUILDING
 OFFICIAL SHALL INCLUDE THE FOLLOWING MINIMUM CRITERIA
 AND DOCUMENTS: A FLOOR PLAN; SITE PLAN; FOUNDATION
 PLAN; FLOOR/ROOF FRAMING PLAN OR TRUSS LAYOUT; AND ALL
 EXTERIOR ELEVATIONS:
  
 COMMERCIAL BUILDINGS:
  
 BUILDING
  
 1. SITE REQUIREMENTS:
 1A) SITE PLAN NOR THE FLOOR PLAN PROVIDE THE FINISH
 FLOOR ELEVATION. THIS PROJECT IS LOCATED IN A FLOOD
 ZONE A9 WITH A FINISH FLOOR ELEVATION OF 13?-6? NGVD.
 FBC BUILDING 3110.1.2 / CITY OF WPB CODE OF ORDINANCES
 SECTION 94-546. STRUCTURE IS LOCATED IN AN "A" FLOOD
 ZONE. A FLOOD ELEVATION CERTIFICATE WILL BE REQUIRED.
  
 FEMA FORM OMB NO. 1660-0008 EXPIRES:
 MARCH 31, 2012.
 FEMA'S NEW ELEVATION CERTIFICATE (EC) WAS APPROVED FOR
 USE, EFFECTIVE MARCH 16, 2009, THROUGH MARCH 31, 2012.
 THE NEW EC WILL BE PHASED IN ON A VOLUNTARY BASIS UNTIL
 MARCH 31, 2010. ALTHOUGH THE OLD VERSION OF THE FORM IS
 NO LONGER AVAILABLE FOR DISTRIBUTION, EXISTING COPIES
 MAY BE USED UNTIL MARCH 31, 2010. ELEVATIONS CERTIFIED
 ON OR AFTER APRIL 1, 2010, MUST BE SUBMITTED ON THE NEW
 FORM.
  
 ADDITIONAL INFORMATION ON THE DIFFERENCES, THE NEW
 FORM, AND INSTRUCTIONS ARE AVAILABLE AT:
 HTTP://WWW.FEMA.GOV/BUSINESS/NFIP/ELVINST.SHTM
  
 1B) TWO BUILDINGS ON THE SAME LOT IT APPEARS TO HAVE
 15? BETWEEN BUILDINGS, THE SITE PLAN INDICATES THE
 EXISTING BUILDING AS A TYPE V, PLANS DO NOT INDICATE IF
 A OR B?
  
 1C) THE SITE PLAN NEW BUILDING DOES NOT DECLARE THE
 MINIMUM BUILDING TYPE FOR THE NEW SANCTUARY?
  
 1D) ARE THE TWO BUILDINGS TO BE CONSIDERED A SEPARATE
 BUILDING IN AREA PER FBC-B 503.1.2 OR IS THERE TO BE
 AND ASSUMED PROPERTY LINE?
  
 2. SITE PLAN INDICATES THE USAGE OF THE BUILDING AS A
 NEW SANCTUARY DECLARE OCCUPANCY TYPE.
  
 3. MINIMUM TYPE OF CONSTRUCTION SHALL BE DETERMINED
 (SEE TABLE 503).
  
 4. FIRE-RESISTANT CONSTRUCTION REQUIREMENTS SHALL
 INCLUDE THE FOLLOWING COMPONENTS:
  
 4A)FIRE-RESISTANT SEPARATIONS TABLE 602
  
 4B) FIRE-RESISTANT PROTECTION FOR TYPE OF CONSTRUCTION
  
 TABLE 6014C) PROTECTION OF OPENINGS TABLE 704.8
  
 5. IS THE BUILDING TO BE FIRE SPRIKLERED OR NOT? ARE
 FIRE SPRINKLERS REQUIRED?
  
 6. OCCUPANCY LOAD/EGRESS REQUIREMENTS SHALL INCLUDE:
 OCCUPANCY LOAD
 GROSS
 NET
 MEANS OF EGRESS
 EXIT ACCESS
 EXIT
 EXIT DISCHARGE
 DOORS
 EMERGENCY LIGHTING AND EXIT SIGNS
 SPECIFIC OCCUPANCY REQUIREMENTS: PANIC HARDWARE FOR
 ASSEMBLY OVER 100 OCCUPANTS
  
 7. STRUCTURAL REQUIREMENTS SHALL INCLUDE:
  
 7.1) SOIL CONDITIONS/ANALYSIS 1802.4 INVESTIGATION.
 TERMITE PROTECTION 2603.8(1-2)
  
 7.2) DESIGN LOADS: PLEASE PROVIDE THE MANUFACTURER SPEC
 & REPORTS FOR REWARD I-FORM PROVIDE CODE COMPLIANCE FOR
 USAGE IN A 140 MPH 3 SECOND GUST WIND ZONE. SHEET S1.01
 FOUNDATION & WALL REINFORCEMENT PLAN ILLUSTRATES THE
 USES OF REINFORCEMENT PLACEMENT AS IF INSTALLED IN CMU
 (CONCRETE MASONRY UNIT) DESIGN. SHEET S1.02 INDICATES
 THE USAGE OF REWARD WALL SYSTEM, ENTIRELY DIFFERENT FOR
 THE ABOVE MENTIONED.
  
 PLEASE PROVIDE COMPLIANCE WITH FBC-B 1918.(1 & 2)
 .1918.1 REINFORCED CONCRETE COMPONENTS. THE DESIGN AND
 CONSTRUCTION OF REINFORCED CONCRETE COMPONENTS FOR
 BUILDINGS SITED IN AREAS WITH A BASIC WIND SPEED
 GREATER THAN 100 MPH (45 M/S) IN ACCORDANCE WITH FIGURE
 1609 SHALL CONFORM TO THE REQUIREMENTS OF ACI 318 OR
 WITH SECTION 1609.1.1, EXCEPTION 3, AS APPLICABLE,
 EXCEPT AS MODIFIED IN THIS SECTION
 1918.2 INSULATED CONCRETE FORM WALL. INSULATED CONCRETE
 FORM (ICF) WALL CONSTRUCTION FOR BUILDINGS SHALL BE IN
 ACCORDANCE WITH ACI 318 OR WITH SECTION 1609.1.1,
 EXCEPTION 3, AS APPLICABLE.
 PLEASE NOTE THAT EXEMPTION 3 ALLOWS FOR THE DESIGN
 GUIDE IBHS GUIDELINES FOR HURRICANE RESISTANT
 CONSTRUCTION PROVIDES A PRESCRIPTIVE REQUIREMENTS FOR
 BUILDINGS OF R2 & R3 OCCUPANCIES.
  
 THE DESIGNER DOES HAVE THE OPTION OF FBC-B 104.9
 APPROVED MATERIALS AND EQUIPMENT. MATERIALS, EQUIPMENT
 AND DEVICES APPROVED BY THE BUILDING OFFICIAL SHALL BE
 CONSTRUCTED AND INSTALLED IN ACCORDANCE WITH SUCH
 APPROVAL.
  
 104.9.1 USED MATERIALS AND EQUIPMENT. THE USE OF USED
 MATERIALS WHICH MEET THE REQUIREMENTS OF THIS CODE FOR
 NEW MATERIALS IS PERMITTED. USED EQUIPMENT AND DEVICES
 SHALL NOT BE REUSED UNLESS APPROVED BY THE BUILDING
 OFFICIAL.
  
 7.3) WIND REQUIREMENTS ARE SHOWN ON SHEET S1.01:
 7.3.1) THE WIND DESIGN IS SHOWN TO HAVE AN EXPOSURE
 ?B?, PLEASE REVIEW SECTION 1609.4.3 EXPOSURE
 CATEGORIES, EXPOSURE C.
  
 THIS EXPOSURE SHALL ALSO APPLY TO ANY BUILDING LOCATED
 WITHIN EXPOSURE B-TYPE TERRAIN WHERE THE BUILDING IS
 WITHIN 100 FEET HORIZONTALLY IN ANY DIRECTION OF OPEN
 AREAS OF EXPOSURE C-TYPE TERRAIN THAT EXTENDS MORE THAN
 600 FEET (182.9 M) AND WIDTH GREATER THAN 150 FT. IN
 THE UPWIND DIRECTION.
  
 7.3.2 BUILDING ENVELOPE: MULTIPLE ISSUES:
 COMPONENTS & CLADDING ,1609, WALL OPENINGS, PRESSURES
 WILL BE GREATER FOR A ?C? EXPOSURE WITH HEIGHT
 MULTIPLIERS OF 1.35 FOR A BUILDING WITH A MEAN ROOF
 HEIGHT OF 25 FEET. PLEASE PROVIDE PRESSURES FOR 10 SQ
 FT FOR BOTH ZONES 4 & 5 SINCE THESE ARE THE WORST CASE
 FOR INTERIOR ZONES AND END ZONES. FURTHER
 IDENTIFICATION OF EFFECTIVE WIND AREA (20 SQ FT, 50 SQ
 FT) AND ASSOCIATED PRESSURES WOULD BE APPRECIATED.
  
 PLEASE PROVIDE ROOF PRESSURES FOR ZONES 1,2 &3 FOR BOTH
 THE SLOPED ROOF AND FLAT ROOF.
  
 7.3.3 106.3.3 PRODUCT APPROVALS. THOSE PRODUCTS WHICH
 ARE REGULATED BY THE DCA RULE 9B-72 SHALL BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD PRIOR
 TO SUBMITTAL FOR JURISDICTIONAL APPROVAL.
  
 FLORIDA DEPARTMENT OF COMMUNITY AFFAIRS RULE 9N-3 NOV.
 01/ 2010 (31) SUB-CATEGORY OF PRODUCTS OR CONSTRUCTION
 SYSTEMS THAT WILL REQUIRE PRODUCT APPROVALS:
 (31)(A) EXTERIOR DOORS.
 (B) WINDOWS
 (C) PANEL WALLS: STOREFRONTS, CURTAIN WALLS, WALL
 LOUVERS, EFIS SYSTEMS,
 (D) ROOFING PRODUCTS AND ASSEMBLIES
 (E) SHUTTERS
 (G) PRE-ENGINEERED A/C STANDS
  
 7.4 STRUCTURAL CALCULATIONS: WALL SYSTEMS 1918.2
 INSULATED CONCRETE FORM WALL SYSTEM.
  
 7.5) FOUNDATION: FOUNDATION DESIGN MAY VERY DEPENDING
 ON THE TYPE OF WALL SYSTEM
  
 7.6) ROOF SYSTEMS : SHEET A-2.01 INDICATES THE TYPE OF
 TRUSS TO BE INSTALLED, WITH CATHEDRAL CEILING BUT NO
 ROOF PLAN IDENTIFYING TRUSSES, LOADS TO BE RESISTED,
 UPLIFT, SLIDING AND GRAVITY LOADS, PART OF THE MWFRS
 (MAIN WIND FORCE RESISTING SYSTEM). 1609 WIND .
  
 8). MATERIALS SHALL BE REVIEWED AND SHALL AT A MINIMUM
 INCLUDE THE FOLLOWING:
 8.1) FOAM INSULATION TO COMPLY WITH FBC-B 2603.4
 THERMAL BARRIER REQUIREMENTS.
  
 8.2 HOW THE INTERIOR WALLS WILL BE ATTACHED TO THE FOAM
 INSULATING BLOCKS?
  
 8.3 PLANS ARE SILENT ON WHAT TYPE OF INSULATION TO BE
 INSTALLED AT THE ROOF SYSTEM, PLEASE NOTE THE PITCH OF
 THE BOTTOM CHORD OF THE TRUSS.
  
 9) PLEASE PROVIDE ENERGY CALCULATIONS FOR THE PROJECT
 FBC-B 13-400.0 METHODS OF COMPLIANCE .
  
  
 10). INTERIOR REQUIREMENTS SHALL INCLUDE THE FOLLOWING:
 INTERIOR FINISHES PER TABLE 803.5.
  
 11) SHEET A-2.1 INDICATES THE USE OR INSTALATION OF A
 STEEPLE ON THE ROOF, NO DETAILS AS TO THE STRUCTURAL
 TIE DOWN NOR MANUFACTURER SPEC. 106.1.2 ADDITIONAL
 INFORMATION REQUIRED.
  
 12)) BEFORE A PERMIT TO CONSTRUCT, MAY BE ISSUED,
 IMPACT FEES MUST BE PAID TO PALM BEACH COUNTY. THE
 ACTUAL PERMIT SET OF PLANS MUST BE STAMPED BY THAT
 OFFICE, AND A COPY OF THE PAID RECEIPT ATTACHED TO THE
 PERMIT APPLICATION. PLEASE CALL (561)233-5025 FOR MORE
 INFORMATION.
  
 A THOROUGH REVIEW CAN NOT BE MADE AT THIS TIME, AS A
 RESULT OF THE ADDITIONAL INFORMATION REQUESTED
 ADDITIONAL COMMENTS MAY APPEAR THAT WERE NOT PART OF
 THIS REVIEW.
  
 JAMES A. WITMER CBO
 SENIOR COMMERCIAL COMBINATION PLANS EXAMINER
 TEL: 561-805-6715
 FAX: 561-805-6676
 E-MAIL: [email protected]
  