| 2012-04-25 16:04:48 | RESIDENTIAL (R3) RENOVATION BUILDING REVIEW COMMENTS. |
| | 2007 FBC-EXISTING BUILDING. FLORIDA RESIDENTIAL CODE |
| | WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS AS REQUIRED BY SEC. |
| | N1100.3. COORDINATE INFORMATION WITH ITEM #2 BELOW. |
| | PLEASE MAKE SURE ALL THE INFORMATION IS COMPLETED IN |
| | THE FORM AND OWNER/AGENT SIGNS AND DATES FORM ALSO. |
| | |
| | 2- SEC R806.1 REQUIRES ROOF VENTILATION. OTHERWISE |
| | UNVENTED ATTIC NEEDS TO BE DESIGNED BY AN ARCHITECT OR |
| | ENGINEER. ENGINEER OF RECORD TO PROVIDE COMPLETE |
| | DETAIL/S SPECS ON PLANS AS REQUIRED BY SEC. R806.1 AND |
| | R806.4. |
| | |
| | 3- PROVIDE CURRENT ESR REPORT FOR THE ICYNENE |
| | INSULATION TO BE INSTALLED. REPORT SUBMITTED IS |
| | EXPIRED. VISIT THE ICC WEBSITE AND DOWNLOAD CURRENT |
| | REPORT. |
| | |
| | 4- FLAT ROOF PRODUCT APPROVAL: PROVIDE SIGNED AND |
| | SEALED RAS 117 CALCULATIONS (2 COPIES) AS REQUIRED BY |
| | GENERAL LIMITATION #7 ON LAST PAGE OF NOA 09-0224.01 |
| | SUBMITTED. NEED CALCULATIONS TO MEET THE DESIGN |
| | PRESSURES REQUIRED BY SEC. R301.2.1.4.3. |
| | |
| | 5- SHEET A-1: |
| | A) SPECIFY EMERGENCY EGRESS FROM MASTER BEDROOM AS |
| | REQUIRED BY SEC. R310. SPECIFY WINDOW WIDTH, WINDOW |
| | HEIGHT AND TOTAL CLEAR OPEN AREA. |
| | |
| | B) IDENTIFY EGRESS WINDOWS ON FIRST FLOOR BEDROOMS |
| | WINDOWS TO VERIFY COMPLIANCE WITH SEC. R310. |
| | |
| | C) DESIGN PARAMETERS. REVISE ALTERATION TYPE SPECIFIED. |
| | THIS IS NOT ALTERATION TYPE II. SEE CHAPTER 4 OF 2007 |
| | FBC-EXISTING BUILDING AND REVISE CLASSIFICATION OF WORK |
| | AS REQUIRED. |
| | |
| | 6- SPECIFY SAFETY GLASS FOR WINDOW IN NOOK AREA, MASTER |
| | BATHROOM WINDOWS BY THE TUB AREA AS REQUIRED BY SEC. |
| | R308.4 |
| | |
| | 7- SHEET S-1: SPECIFY OVERFLOW SCUPPERS AS REQUIRED BY |
| | SEC. R903.4.1. |
| | |
| | 8- SHEET S-2: REVISE DETAIL 1/S-2. RISER AND TREAD |
| | RATIO DOESN'T COMPLY WITH SEC. R311.5.3.2. |
| | |
| | 9- DRAWINGS S-2 AND S-3 ARE MISSING ENGINEER'S SEAL AS |
| | REQUIRED BY CHAPTER 471 FLORIDA STATUTE. ONLY ONE SET |
| | OF PLANS HAS THE SEAL. NEED SEAL ON THE OTHER SET. |
| | |
| | 10- PROVIDE PRODUCT APPROVAL (2 COPIES) FOR ALL THE |
| | SIMPSON STRUCTURAL COMPONENTS SPECIFIED ON PLANS AND |
| | DETAILS AS REQUIRED BY DCA RULE 9N-3. |
| | |
| | 11- ENGINEER OF RECORD TO REVIEW AND APPROVE IN WRITING |
| | (NOT SIGNING AND SEALING) ALL PRODUCT APPROVALS AS |
| | REQUIRED BY SEC. 106.3.3 CITY AMENDMENTS TO FBC. |
| | |
| | 12- PROVIDE COMPLETE DETAIL/SPECIFICATIONS FOR NEW |
| | TRELLIS SHOWN ON SHEET SP-1. NO INFORMATION WAS |
| | SUBMITTED. |
| | |
| | IF YOU HAVE ANY QUESTIONS, PLEASE CALL |
| | JULIO GOMEZ |
| | COMMERCIAL COMBINATION PLANS EXAMINER |
| | (561)805-6712 |
| | |