Plan Review Notes
Plan Review Notes For Permit 12030360
Permit Number 12030360
Review Stop B
Sequence Number 3
Notes
Date Text
2012-03-27 14:50:10RE-ROOF BUILDING REVIEW THIRD CHECKLIST.
 2007 BC WITH 2009 REVISIONS.
  
 ***ORIGINAL COMMENT:
 1- PROVIDE ACTUAL RAS 117 CALCULATIONS SHOWING
 COMPLIANCE WITH THE NAIL ENHANCING SHOWN FOR THE
 PROPOSED NAIL ENHANCING ON ROOF ZONE 2 AND 3. IT LOOKS
 LIKE THE PROPOSED NAIL ENHANCING DOESN'T MEET THE
 CALCULATED DESIGN PRESSURES FOR ROOF ZONE 3. PAGE 10 OF
 14 OF NOA SUBMITTED SHOWS MEMBRANE WITH 57" TABS SYSTEM
 WITH THE SAME FASTENER SPACING (6"O.C.) WITH A MAXIMUM
 DESIGN PRESSURE OF -105.0PSF.
 SEC. 106.1.2 CITY AMENDMENTS TO FBC.
  
 ***NO ENGINEER RESPONSE TO THIS ITEM. NO CALCULATIONS
 WERE SUBMITTED.
  
 2- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO
 LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION WAS
 UPDATED. OWES $432.18.
  
 JULIO GOMEZ
 COMMERCIAL COMBINATION PLANS EXAMINER
 (561)805-6712