| Plan Review Notes For Permit 12030360 |
| Permit Number |
12030360 |
|
| Review Stop |
B |
| Sequence Number |
2 |
|
| Notes |
| Date |
Text |
| 2012-03-19 11:09:16 | RE-ROOF RE-SUBMITTAL BUILDING REVIEW COMMENTS. | | | 2007 BC WITH 2009 REVISIONS. | | | | | | 1- GENERAL LIMITATION #5 ON LAST PAGE OF NOA 07-1018.10 | | | SUBMITTED REQUIRES A FIELD WITHDRAWAL TEST (TAS 105). | | | NEED TO PROVIDE THE TAS 105 REPORT AND THE REQUIRED | | | SIGNED AND SEALED RAS 117 CALCULATIONS BASED ON THE | | | TEST RESULTS. | | | | | | 2- PROVIDE ACTUAL RAS 117 CALCULATIONS SHOWING | | | COMPLIANCE WITH THE NAIL ENHANCING SHOWN FOR THE | | | PROPOSED NAIL ENHANCING ON ROOF ZONE 2 AND 3. IT LOOKS | | | LIKE THE PROPOSED NAIL ENHANCING DOESN'T MEET THE | | | CALCULATED DESIGN PRESSURES FOR ROOF ZONE 3. PAGE 10 OF | | | 14 OF NOA SUBMITTED SHOWS MEMBRANE WITH 57" TABS SYSTEM | | | WITH THE SAME FASTENER SPACING (6"O.C.) WITH A MAXIMUM | | | DESIGN PRESSURE OF -105.0PSF. | | | SEC. 106.1.2 CITY AMENDMENTS TO FBC. | | | | | | 3- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO | | | LOW. SEC. 108.3 CITY AMENDMENTS TO FBC. VALUATION WAS | | | UPDATED. OWES $432.18. | | | | | | JULIO GOMEZ | | | COMMERCIAL COMBINATION PLANS EXAMINER | | | (561)805-6712 |
|