| Plan Review Notes For Permit 12030357 |
| Permit Number |
12030357 |
|
| Review Stop |
FIRE |
| Sequence Number |
1 |
|
| Notes |
| Date |
Text |
| 2012-03-16 12:33:24 | 03/16/2012 PLANS REVIEWED BY FIRE **APPROVED** | | | | | | 1.) A MANUAL ACTIVATION DEVICE SHALL BE LOCATED ALONG | | | THE EGRESS PATH AND BE A MINIMUM OF 10 FEET AND A | | | MAXIMUM OF 20 FEET FROM THE KITCHEN EXHAUST SYSTEM. THE | | | DEVICE SHALL BE MOUNTED 42-48 INCHES ABOVE THE FLOOR | | | AND SHALL CLEARLY IDENTIFY THE HAZARD PROTECTED PER FBC | | | 904.11.1. | | | | | | DERRICK L. DANIELS, BATTALION CHIEF | | | WEST PALM BEACH FIRE RESCUE | | | FIRE & LIFE SAFETY PLAN REVIEW | | | (561) 805-6722 | | | |
|