| Date |
Text |
| 2012-04-11 07:55:34 | 2007 FBC W/2009 REVISIONS |
| | |
| | DENIED BY BUILDING |
| | |
| | 1) SUBMIT TWO SETS OF A SUBSURFACE SOIL TEST TO |
| | DETERMINE THE BEARING CAPACITY OF THE SOIL. FBC R401.4 |
| | |
| | 2) THE STRUCTURE IS LOCATED IN A 140 MPH WINDSPEED AND |
| | IS EXPOSURE CATEGORY C. PLEASE SPECIFY THIS DESIGN |
| | REQUIREMENT INFORMATION ON THE PLANS.FBC R301.1 AND |
| | R301.2.1.4.3 |
| | |
| | 3) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE |
| | INTERCOASTAL WATERWAY WHICH REQUIRES THE ROOF SHEATHING |
| | UPLIFT AND ROOF TO WALL UPLIFT LOADS TO BE INCREASED BY |
| | 20 PERCENT BY FBC R301.2.1.4.3 (2). |
| | |
| | 4) THE CONSTRUCTION TYPE SPECIFIED ON THE PLANS IS TYPE |
| | III-B. THIS TYPE OF CONSTRUCTION REQUIRES 2 HOUR FIRE |
| | RATED EXTERIOR WALLS. THE COMMON CONCRETE BLOCK DOES |
| | NOT PROVIDE A TWO HOUR FIRE RATING. SHOW HOW THE |
| | REQUIRED RATING WILL BE ACHIEVED. NOTE: THE LEAST |
| | RESTRICTIVE ALLOWABLE CONSTRUCTION TYPE FOR THIS |
| | STRUCTURE IS TYPE V-B WHICH DOES NOT REQUIRE ANY FIRE |
| | RATED ASSEMBLIES. YOU MAY WISH TO DECLARE THIS |
| | CONSTRUCTION TYPE ON THE PLANS. |
| | |
| | 5) SUBMIT TWO COPIES OF A SURVEY / SITE PLAN THAT |
| | INDICATES THE DISTANCE TO PROPERTY LINES AND OTHER |
| | STRUCTURES LOCATED ON THE SAME LOT. FBC R302.1 |
| | |
| | 6) THE DRAWING INDEX ON PLAN SHEET A0.0 LISTS A SHEET |
| | S-1.0 FOUNDATION PLAN AND DETAILS WHICH WAS MISSING |
| | FROM THE PLANS. PLEASE SUBMIT MISSING PLANS. CITY |
| | AMENDMENTS 106.3.5.4 |
| | |
| | 7) SHEET A-3.0 WAS ALSO LISTED IN THE DRAWING INDEX BUT |
| | MISSING FROM THE PLANS. PLEASE SUBMIT MISSING PLANS. |
| | CITY AMENDMENTS 106.3.5.4 |
| | |
| | 8) PROVIDE WALL SECTIONS AND A WALL SCHEDULE |
| | IDENTIFYING THE WALL TYPES ON THE PLANS. CITY |
| | AMENDMENTS 106.3.5.4 |
| | |
| | 9) SUBMIT A WINDOW AND DOOR SCHEDULE ON THE PLANS. CITY |
| | AMENDMENTS 106.3.5.4 |
| | |
| | 10) SPECIFY THE REQUIRED EXTERIOR DOOR AND WINDOW |
| | DESIGN PRESSURES ON THE PLANS. FBC R301.2.1 |
| | |
| | 11) CALL OUT THE COLUMN TYPES AT THE LOCATIONS ON THE |
| | PLANS. CITY AMENDMENTS 106.3.5.4 |
| | |
| | 12) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH |
| | THE NEW TRUSSES AT THE EXISTING WALLS. CITY AMENDMENTS |
| | 106.3.5.4 |
| | |
| | 13) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE |
| | SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT. |
| | 2007 FBC ENERGY GLITCH AMENDMENTS N1100.2 |
| | |
| | 14) ICYNENE SPRAY FOAM INSULATION IS TYPICALLY APPLIED |
| | TO THE UNDERSIDE OF THE ROOF SHEATHING WITH AN |
| | UN-VENTED ATTIC. THE ENERGY CALCULATIONS SPECIFY A |
| | VENTED ATTIC. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1 |
| | |
| | 15) SUBMIT TWO COPIES OF MANUFACTURES SPECIFICATIONS AN |
| | EVALUATION REPORT FOR THE ICYNENE SPRAY FOAM |
| | INSULATION. FBC R314 |
| | |
| | 16) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE |
| | EXTERIOR DOORS AND WINDOWS, STRUCTURAL MULLIONS AND |
| | ROOFING MATERIAL AS REQUIRED BY DCA RULE 9B-72. |
| | |
| | 17) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED |
| | AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR |
| | THE PROJECT. CITY AMENDMENTS 106.3.3 |
| | |
| | 18) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW |
| | EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED. |
| | |
| | ROBERT MCDOUGAL |
| | BLDG. PLAN REVIEW |
| | (561)805-6714 |
| | [email protected] |