Plan Review Notes
Plan Review Notes For Permit 12030345
Permit Number 12030345
Review Stop B
Sequence Number 1
Notes
Date Text
2012-04-11 07:55:342007 FBC W/2009 REVISIONS
  
 DENIED BY BUILDING
  
 1) SUBMIT TWO SETS OF A SUBSURFACE SOIL TEST TO
 DETERMINE THE BEARING CAPACITY OF THE SOIL. FBC R401.4
  
 2) THE STRUCTURE IS LOCATED IN A 140 MPH WINDSPEED AND
 IS EXPOSURE CATEGORY C. PLEASE SPECIFY THIS DESIGN
 REQUIREMENT INFORMATION ON THE PLANS.FBC R301.1 AND
 R301.2.1.4.3
  
 3) THE STRUCTURE IS LOCATED WITHIN 600 FEET OF THE
 INTERCOASTAL WATERWAY WHICH REQUIRES THE ROOF SHEATHING
 UPLIFT AND ROOF TO WALL UPLIFT LOADS TO BE INCREASED BY
 20 PERCENT BY FBC R301.2.1.4.3 (2).
  
 4) THE CONSTRUCTION TYPE SPECIFIED ON THE PLANS IS TYPE
 III-B. THIS TYPE OF CONSTRUCTION REQUIRES 2 HOUR FIRE
 RATED EXTERIOR WALLS. THE COMMON CONCRETE BLOCK DOES
 NOT PROVIDE A TWO HOUR FIRE RATING. SHOW HOW THE
 REQUIRED RATING WILL BE ACHIEVED. NOTE: THE LEAST
 RESTRICTIVE ALLOWABLE CONSTRUCTION TYPE FOR THIS
 STRUCTURE IS TYPE V-B WHICH DOES NOT REQUIRE ANY FIRE
 RATED ASSEMBLIES. YOU MAY WISH TO DECLARE THIS
 CONSTRUCTION TYPE ON THE PLANS.
  
 5) SUBMIT TWO COPIES OF A SURVEY / SITE PLAN THAT
 INDICATES THE DISTANCE TO PROPERTY LINES AND OTHER
 STRUCTURES LOCATED ON THE SAME LOT. FBC R302.1
  
 6) THE DRAWING INDEX ON PLAN SHEET A0.0 LISTS A SHEET
 S-1.0 FOUNDATION PLAN AND DETAILS WHICH WAS MISSING
 FROM THE PLANS. PLEASE SUBMIT MISSING PLANS. CITY
 AMENDMENTS 106.3.5.4
  
 7) SHEET A-3.0 WAS ALSO LISTED IN THE DRAWING INDEX BUT
 MISSING FROM THE PLANS. PLEASE SUBMIT MISSING PLANS.
 CITY AMENDMENTS 106.3.5.4
  
 8) PROVIDE WALL SECTIONS AND A WALL SCHEDULE
 IDENTIFYING THE WALL TYPES ON THE PLANS. CITY
 AMENDMENTS 106.3.5.4
  
 9) SUBMIT A WINDOW AND DOOR SCHEDULE ON THE PLANS. CITY
 AMENDMENTS 106.3.5.4
  
 10) SPECIFY THE REQUIRED EXTERIOR DOOR AND WINDOW
 DESIGN PRESSURES ON THE PLANS. FBC R301.2.1
  
 11) CALL OUT THE COLUMN TYPES AT THE LOCATIONS ON THE
 PLANS. CITY AMENDMENTS 106.3.5.4
  
 12) SPECIFY THE CONNECTORS THAT WILL BE USED TO ATTACH
 THE NEW TRUSSES AT THE EXISTING WALLS. CITY AMENDMENTS
 106.3.5.4
  
 13) THE ENERGY CALCULATION FORMS ARE REQUIRED TO BE
 SIGNED AND DATED BY THE PREPARER AND THE OWNER/AGENT.
 2007 FBC ENERGY GLITCH AMENDMENTS N1100.2
  
 14) ICYNENE SPRAY FOAM INSULATION IS TYPICALLY APPLIED
 TO THE UNDERSIDE OF THE ROOF SHEATHING WITH AN
 UN-VENTED ATTIC. THE ENERGY CALCULATIONS SPECIFY A
 VENTED ATTIC. PLEASE CLARIFY. CITY AMENDMENTS 106.1.1
  
 15) SUBMIT TWO COPIES OF MANUFACTURES SPECIFICATIONS AN
 EVALUATION REPORT FOR THE ICYNENE SPRAY FOAM
 INSULATION. FBC R314
  
 16) SUBMIT TWO COPIES OF PRODUCT APPROVALS FOR THE
 EXTERIOR DOORS AND WINDOWS, STRUCTURAL MULLIONS AND
 ROOFING MATERIAL AS REQUIRED BY DCA RULE 9B-72.
  
 17) THE PRODUCT APPROVALS ARE REQUIRED TO BE REVIEWED
 AND APPROVED IN WRITING BY THE DESIGNER OF RECORD FOR
 THE PROJECT. CITY AMENDMENTS 106.3.3
  
 18) PLEASE PROVIDE A RESPONSE LETTER INDICATING HOW
 EACH OF THE REVIEW COMMENTS HAS BEEN ADDRESSED.
  