2012-04-03 13:46:345300 EAST AVENUE
 PERMIT #12030344
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF
 THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE
 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA
 AMENDMENTS.
  
 TRASH AND CONSTRUCTION DEBRIS SHALL BE REMOVED FROM THE
 SITE DAILY. ALL DEMOLITION AND CONSTRUCTION AREAS SHALL
 HAVE "NO SMOKING" SIGNS POSTED.
  
 FIRE PROTECTION SYSTEMS SHALL REMAIN ACTIVE DURING
 DEMOLITION AND RENOVATION ACTIVITIES. IN THE EVENT A
 FIRE PROTECTION SYSTEM IS OUT OF SERVICE FOR MORE THAN
 4-HOURS IN A 24-HOUR PERIOD, THE BUILDING SHALL BE
 PLACED UNDER A FIRE WATCH. ALL FIRE WATCH REQUESTS MUST
 BE SUBMITTED IN WRITING AND APPROVED BY THE OFFICE OF
 THE FIRE MARSHAL LOCATED AT 500 NORTH DIXIE HIGHWAY.
  
 SHEET D1 INDICATES THE BUILDING WILL BE OCCUPIED IN
 SPACES ADJACENT TO CONSTRUCTION/DEMOLITION ACTIVITIES.
 TO ENSURE THE SAFETY OF THE OCCUPANTS, PROVIDE A
 DETAILED CONSTRUCTION/DEMOLITION PHASING PLAN SHOWING
 TEMPORARY SEPARATION WALLS, FUNCTIONING/NON-FUNCTIONING
 EXITS, TRAVEL DISTANCES, EXIT SIGNS, FIRE
 EXTINGUISHERS, ETC.
  
 COULD NOT LOCATE SMOKE DETECTION DEVICES ON SECOND
 FLOOR.
  
 COULD NOT LOCATE EMERGENCY LIGHTING ON SECOND FLOOR.
  
 COULD NOT LOCATE PORTABLE FIRE EXTINGUISHER LOCATIONS
 ON THE SECOND FLOOR.
  
 ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE
 REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE
 BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN
 THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED
 CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE
  