Plan Review Notes
Plan Review Notes For Permit 12030344
Permit Number 12030344
Review Stop B
Sequence Number 1
Notes
Date Text
2012-03-26 11:23:12BUILDING PROVISO:
 SHEET A10 SECOND FLOOR PARTIAL FLOOR PLAN
 PLEASE REVIEW PLANS FOR: 2007/09 FBC-B 11-4.13.7
 TWO DOORS IN SERIES. THE MINIMUM SPACE BETWEEN TWO
 HINGED
 OR PIVOTED DOORS IN SERIES SHALL BE 48 INCHES (1219 MM)
 PLUS THE
 WIDTH OF ANY DOOR SWINGING INTO THE SPACE. DOORS IN
 SERIES SHALL
 SWING EITHER IN THE SAME DIRECTION OR AWAY FROM THE
 SPACE BETWEEN
 THE DOORS [SEE FIGURE 26(A)].
 LOCATIONS:
 1) ENTRY AREA LEADING INTO CORRIDOR # 224
 2) ENTRY AREA LEADING INTO LOBBY, ROOM 213
 3) ENTRY DOOR INTO STAIR WELL #1 & 4
 IN THE ABOVE CASES TWO AREAS BUT 3 DOORS IN EACH AREA
  
  