| 2012-03-22 16:42:42 | BUILDING PLAN REVIEW | | | PERMIT: 12030343 | | | ADD: 5300 EAST AVENUE | | | CONT: TRILLION CONSTRUCTION | | | TEL: (561)283-512 | | | 1 | | | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS | | | * WEST PALM BEACH AMENDMENTS | | | | | | 2007 EXISTING BUILDING CODE LEVEL II 701.3 | | | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, | | | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS | | | OF THE FLORIDA BUILDING CODE, BUILDING. | | | | | | 1ST REVIEW | | | ACTION: DENIED | | | | | | 1) BEFORE THIS PERMIT CAN BE ISSUED A FIRE SPRINKLER | | | DETAIL INDICATING COMPLIANCE WITH 2007/09 FBC-B 404.5 | | | EXCEPTION 1. | | | | | | 2007/09 FBC-B 404.5 EXCEPTION 1. A GLASS WALL FORMING A | | | SMOKE PARTITION WHERE AUTOMATIC SPRINKLERS ARE SPACED 6 | | | FEET (1829 MM) OR LESS ALONG BOTH SIDES OF THE | | | SEPARATION WALL, OR ON THE ROOM SIDE ONLY IF THERE IS | | | NOT A WALKWAY ON THE ATRIUM SIDE, AND BETWEEN 4 INCHES | | | AND 12 INCHES (102 MM AND 305 MM) AWAY FROM THE GLASS | | | AND DESIGNED SO THAT THE ENTIRE SURFACE OF THE GLASS IS | | | WET UPON ACTIVATION OF THE SPRINKLER SYSTEM WITHOUT | | | OBSTRUCTION. | | | | | | JAMES A. WITMER CBO | | | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER | | | TEL: 561-805-6715 | | | FAX: 561-805-6676 | | | E-MAIL: [email protected] | | | | | | |
|