| 2012-04-10 16:33:12 | RESIDENTIAL (R3) ADDITION BUILDING REVIEW COMMENTS. |
| | 2007 FLORIDA RESIDENTIAL CODE WITH 2009 REVISIONS. |
| | |
| | 1- PROVIDE ENERGY CALCULATIONS (2 COPIES) AS REQUIRED |
| | BY SEC. N1100.3. COMPLETE ALL THE INFORMATION ON THE |
| | FORM AND OWNER/AGENT TO SIGN AND DATE BOTTOM OF FORM |
| | ALSO. |
| | |
| | 2- PROVIDE PRODUCT APPROVALS (2 COPIES) AS REQUIRED BY |
| | DCA RULE 9N-3 FOR: |
| | A) WINDOWS TO BE INSTALLED. |
| | B) EXTERIOR DOORS TO BE INSTALLED. |
| | C) STORM SHUTTERS. IF DOORS AND WINDOWS DON'T HAVE |
| | IMPACT GLASS. AND PROVIDE SHUTTERS COMPLETE |
| | INSTALLATION SCHEDULE. |
| | D) PRECAST LINTELS AS SHOWN ON PLANS. |
| | E) SHINGLES AS SHOWN ON PLANS. |
| | |
| | 3- ACCORDING TO SEC. R301.2.1.4.3 THIS BUILDING IS |
| | LOCATED ON EXPOSURE "C" NOT "B". |
| | A) REVISE THE DESIGN INFORMATION ON SHEET #1. |
| | B) REVISE THE COMPONENTS AND CLADDING DESIGN PRESSURES |
| | SHOWN ON SHEET #1. |
| | |
| | 4- SPECIFY CARBON MONOXIDE ALARMS ON PLANS AS REQUIRED |
| | BY SEC. R313.4. |
| | |
| | 5- SHEET #4: SPECIFY SIZE OF ATTIC SCREEN VENTS ON WALL |
| | SECTION. SEC. R806. |
| | |
| | 6- DOOR BUCK DETAIL ON SHEET #4: |
| | A) REVISE SIZE OF BUCK. NEED TO PROVIDE DOOR FRAME FULL |
| | SUPPORT. SEE DOOR PRODUCT APPROVAL FOR REQUIRED SIZE. |
| | SEC. R613.6. |
| | |
| | B) CLARIFY WOOD JAMB ATTACHMENT TO DOOR BUCK. SEE DOOR |
| | PRODUCT APPROVAL AND REVISE AS REQUIRED. SEC. R613.6. |
| | |
| | 7- WINDOW BUCK DETAIL ON SHEET #4: |
| | A) SPECIFY FASTENING OF BUCK. SEC. R613.6. |
| | |
| | B) BEVELED BUCK IS NOT ALLOWED. REVISE AS REQUIRED BY |
| | SEC. R613.6. |
| | |
| | 8- PROVIDE COMPLETE SPECIFICATIONS FOR NEW BOND BEAM. |
| | SPECIFY SIZE AND STEEL REINFORCEMENT. SEC. 106.1.1 CITY |
| | AMENDMENTS TO FBC. |
| | |
| | 9- PROVIDE COMPLETE SPECIFICATIONS FOR THE 8'-0" |
| | MASONRY OPENING ON EXISTING EXTERIOR BEARING WALL TO |
| | ALLOW ACCESS FOR NEW FAMILY ROOM. SEC. 106.1.1 CITY |
| | AMENDMENTS. |
| | |
| | A) SPECIFY TYPE AND SIZE OF EXISTING BEAM. |
| | |
| | B) PROVIDE COMPLETE SPECIFICATIONS FOR COLUMNS AT BOTH |
| | ENDS. |
| | |
| | 10- SHEET #2: THIS IS NOT A LEVEL 2 ALTERATION. THIS IS |
| | AN ADDITION . REVISE AS REQUIRED. |
| | |
| | 11- SPECIFY ATTIC SIZE AND LOCATION FOR NEW ADDITION AS |
| | REQUIRED BY SEC. R807. |
| | |
| | 12- VALUATION DECLARED IN THE PERMIT APPLICATION IS TOO |
| | LOW. SEC. 108.3 CITY AMENDMENTS. VALUATION NEED TO |
| | INCLUDE ALL LABOR, MATERIALS AND DESIGN FEES. VALUATION |
| | WAS UPDATED OWES $831.32. |
| | |