Review Stop FIRE
Sequence Number 3
Notes
Date Text
2012-06-30 18:48:352275 PALM BEACH LAKES BOULEVARD
 PERMIT #12030334
 REVIEW COMMENTS - FIRE DEPARTMENT
  
 REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION
 DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT.
 AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE
 SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS
 (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS)
 FOR A SUB-PERMIT.
  
 TO OBTAIN A GENERAL BUILDING PERMIT, BY STATE LAW AND
 THE FLORIDA BUILDING CODE, WHEN A FIRE SPRINKLER SYSTEM
 IS TO BE INSTALLED OR MODIFIED, PURSUANT TO FS 553.79,
 FIRE PROTECTION DESIGN DOCUMENTS SHALL BE PREPARED BY A
 QUALIFIED ENGINEER AND SUBMITTED TO THE AUTHORITY
 HAVING JURISDICTION. ALL DESIGN DOCUMENTS SUBMITTED FOR
 THIS PURPOSE SHALL PROVIDE A SCOPE OF WORK FOR THE
 SPRINKLER CONTRACTOR AND SHALL COMPLY WITH FBPE RULES
 OF RESPONSIBILITY CHAPTER 61G15-32. PER 61G15-32 FAC,
 BASIC ENGINEERING REQUIREMENTS FOR PLANS SHALL INCLUDE:
 WATER SUPPLY INFORMATION, SUPPRESSION SYSTEM TYPE,
 HAZARD CLASSIFICATION, APPLICABLE CODES AND STANDARDS
 WITH APPROPRIATE YEAR/EDITION, STRUCTURAL INFORMATION
 AND STRUCTURAL OPENINGS, ALARMS, ACTIVATION CONTROLS,
 AND INTERFACES WITH OTHER SYSTEMS. CONTRACTOR SHOP
 DRAWINGS ARE REQUIRED TO OBTAIN A FIRE SPRINKLER
 PERMIT. SHOP DRAWINGS SHALL CONFORM TO THE DESIGN
 REQUIREMENTS OF THE ENGINEER OF RECORD DESIGN
 DOCUMENTS. SHOP DRAWINGS SHALL NOT BE SEALED BY AN
 ENGINEER.
  
 WESLEY JOLIN
 OFFICE OF THE FIRE MARSHAL
 WEST PALM BEACH FIRE RESCUE