| 2012-07-05 12:37:37 | BUILDING PLAN REVIEW |
| | PERMIT: 12030334 |
| | ADD: 2275 PALM BEACH LAKES BLVD |
| | SHILOH FAMILY WORSHIP CENTER - PHASE II |
| | CONT: CUTTING EDGE BUILDING SYSTEMS, INC |
| | TEL: (561)282-8265 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 3RD REVIEW |
| | ACTION: DENIED |
| | INFORMATIONAL: WHEN RESUBMITTING PLANS PLEASE INDICATE |
| | THE REVISION & REMOVE & REPLACE ANY PAGES AS NECESSARY. |
| | A TRANSMITTAL LETTER LISTING THE ORIGINAL REVIEW |
| | COMMENT NUMBER, WITH A DESCRIPTION OF THE REVISION |
| | MADE, IDENTIFYING THE SHEET OR SPECIFICATION PAGE WHERE |
| | THE CHANGES CAN BE FOUND WILL HELP TO EXPEDITE YOUR |
| | PERMIT. THANK YOU FOR YOUR ANTICIPATED COOPERATION. |
| | |
| | THE THIRD SUBMITTAL THE NEW SHEETS HAVE NOT BEEN |
| | INSERTED INTO THE PLANS, AS REVIEWED NOT COMPLETE SETS |
| | OF PLANS. |
| | |
| | 1) COMPLIED. |
| | |
| | 2) COMPLIED. PLANS INDICATE THIS TENANT SPECE TO BE |
| | FIRE SPRINKLERED FIRE SPRINKLER LAYOUT IS INDICATED ON |
| | A2.0 WITH NEW FIRE SPRINKLER NOTE SHOP DRAWINGS TO |
| | FOLLOW WITH HYDROLIC CALCULATIONS. |
| | |
| | 3) COMPLIED. |
| | |
| | 4) COMPLIED. |
| | |
| | 5) PROVISO: SHEET A6.0 & A6.1 INDICATES CLOUDS AS PART |
| | OF A ISOLATED CEILING DESIGN WITHIN THE ASSEMBLY |
| | OCCUPANCY. PLEASE PROVIDE DETAILS ON WHAT TYPE OF |
| | MATERIALS THIS SYSTEM IS COMPOSED OF, HOW IT IS TO BE |
| | HUNG, AND TO WHAT THE CLOUD SYSTEM IS TO BE ATTACHED? |
| | ADDITIONAL INFORMATION IS REQUIRED? 106.1.2. SHOP |
| | DRAWINGS WILL BE REQUIRED TO BE REVIEWED BY THE |
| | DESIGNER OF RECORD BEFORE SUBMITTING THEM TO THE |
| | BUILDING DEPARTMENT. |
| | |
| | 6) THIRD REVIEW, NEW COMMENT, THE NEW A1.0 SHEET IS |
| | MISSING WALL TAGS FOR WALLS THAT WERE CHANGED AS PART |
| | OF THIS REVISION, EXAMPLE STORAGE ROOM WALLS HAVE THE |
| | SAME HASH MARKING AS THE COMMON WALL TO THE RESTROOMS, |
| | THIS WALL DOES NOT REQUIRE THE DRYWALL TO CONTINUE TO |
| | THE DECK ABOVE, WHERE AS THE STORAGE ROOM CONSIDERED A |
| | INCIDENTAL USE AREA AND CONSSTRUCTION TO MEET THE |
| | REQUIREMENT OF 508.2.2.1 AND CAPABLE OF RESITNG PASSAGE |
| | OF SMOKE. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |