| 2012-05-24 10:24:45 | PLANS DENIED | | | 1) PROVIDE A FULL SET OF MECHANICAL PLANS MISSING | | | PAGES M-2, M-3, M-4 | | | 2) REFER TO SECTION 901.1 EXISTING BUILDING CODE | | | 2007. ALL ROOF TOP UNITS NEED TO COMPLY WITH | | | 13-409.AB.3.3 SHUTOFF DAMPER CONTROLS.2007 | | | FLORIDA ENERGY CODE. | | | 3) REFER TO SECTION 607.5.1 FIRE WALLS 2007 | | | FBC (M) MISSING A FIRE DAMPER IN 4X9 DUCT ABOVE | | | WOMENS BATHROOM. | | | PLAN REVIEW BY HAROLD MOSER | | | 561-805-6732 | | | [email protected] |
|