| 2012-05-21 13:38:34 | 2275 PALM BEACH LAKES BOULEVARD |
| | PERMIT #12030334 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | SHEET LS1.0: THE KNOX-BOX SHOWN AS "LB" INCORRECTLY |
| | INDICATES THE AUTHORITY HAVING JURISDICATION AS PALM |
| | BEACH COUNTY FIRE RESCUE. |
| | |
| | SHEET A1.0: KNOX-BOX IS INCORRECTLY IDENTIFIED BY |
| | CONSTRUCTION NOTE #23 (SHOULD BE #24). |
| | |
| | SHEET A 7.2: COULD NOT LOCATE TACTILE SIGNAGE FOR EXIT |
| | DOORS. |
| | |
| | SHEET A7.0: DOOR #9 DOES NOT INDICATE A FIRE RESISTANCE |
| | RATING. |
| | |
| | SHEET A7.0: SINGLE DOOR AT MAIN ENTRANCE IS INDICATED |
| | AS DOOR #7; THE SCHEDULE INDICATES DOOR #7 AS A STORAGE |
| | ROOM DOOR. |
| | |
| | SHEET A7.0: FIRE RATED DOORS ON STORAGE ROOMS NEED TO |
| | BE EQUIPPED WITH DOOR CLOSERS. |
| | |
| | SHEET A1.0 & SHEET A6.1: STAIRS TO PLATFORM ARE NOT |
| | SHOWN ON SHEET A1.0. THE RAISED PLATFORM IS INDICATED |
| | AS AN ELEVATION OF 3'-6". PROVIDE STAIR GUARDS |
| | RESISTING 4-INCH SPHERE AND A PERIMETER GUARDRAIL FOR |
| | THE UPPER PLATFORM. |
| | |
| | NOTE: ENGINEERED FIRE ALARM PLANS NOT RESUBMITTED: |
| | REPEAT COMMENT: PER LOCAL AHJ POLICY, DUCT SMOKE |
| | DETECTORS SHALL INITIATE A GENERAL FIRE ALARM |
| | CONDITION. |
| | |
| | REPEAT COMMENT: PROVIDE A PRE-RECORDED FIRE ALARM |
| | EVACUATION MESSAGE NOTIFYING OCCUPANTS AN EMERGENCY HAS |
| | BEEN REPORTED IN THE BUILDING, LOCATE THE NEAREST EXIT, |
| | AND EXIT THE BUILDING IMMEDIATELY. |
| | |
| | REPEAT COMMENT: A CERTIFICATE OF COMPLETION AND A THIRD |
| | PARTY MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE |
| | SHALL BE PROVIDED AT TIME OF FINAL FIRE ALARM |
| | INSPECTION. |
| | |
| | REPEAT COMMENT: ASSEMBLY OCCUPANCIES EXCEEDING 300 |
| | PERSONS WILL BE REQUIRED TO BE PROTECTED BY AN |
| | AUTOMATIC FIRE SPRINKLER SYSTEM. |
| | ADDITIONAL INFORMATION: SECTION 903.2.1.3 OF THE |
| | FLORIDA BUILDING CODE WILL STILL REQUIRE AN AUTOMATIC |
| | SPRINKLER SYSTEM BECAUSE OF THE MIXED OCCUPANCY |
| | (ASSEMBLY, MERCANTILE, EDUCATION) USAGE. ALSO REFER TO |
| | SECTION 12.3.5.2 AND SECTION 12.3.5.3 (FLORIDA FIRE |
| | PREVENTION CODE - NFPA 101) WHEREBY AN AUTOMATIC |
| | SPRINKLER SYSTEM IS REQUIRED. |
| | |
| | REPEAT COMMENT: ENGINEERED FIRE SPRINKLER CONSTRUCTION |
| | DOCUMENTS ARE REQUIRED FOR A GENERAL BUILDING PERMIT. |
| | AFTER THE BUILDING PERMIT HAS BEEN ISSUED, THE |
| | SUBCONTRACTORS CAN THEN SUBMIT SHOP DRAWINGS |
| | (CONFORMING TO THE ENGINEERED CONSTRUCTION DOCUMENTS) |
| | FOR A SUB-PERMIT. |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |