| 2012-04-05 11:32:12 | FBC 2007 PLUMBING REVIEW #1 | | | DENIED: | | | | | | 1. THE PLUMBING CALCULATIONS ON SHEET G1.0 SHOW 8 WATER | | | CLOSETS FOR WOMEN AND 4 FOR MEN. PLEASE CLARIFY OR | | | CORRECT THE FOLLOWING: | | | 1A. SHEET A1.0 AND PLUMBING SHEETS SHOW ONLY 4 WATER | | | CLOSETS FOR WOMEN. | | | 1B. SHEET A1.0 AND PLUMBING SHEETS SHOW 1 WATER CLOSET | | | AND 3 URINALS FOR MEN. SECTION 419.2 URINALS SHALL NOT | | | BE SUBSTITUTED FOR MORE THAN 67 PERCENT OF THE REQUIRED | | | WATER CLOSETS IN ASSEMBLY AND EDUCATIONAL OCCUPANCIES. | | | 2 WATER CLOSETS AND 2 URINALS WOULD BE REQUIRED. | | | 1C. 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY | | | AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET | | | ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR | | | MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED. | | | | | | 2. SHEET P-2 HOT WATER WILL BE REQUIRED AT THE JANITOR | | | SINK: | | | 607.1 WHERE REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER | | | SHALL BE SUPPLIED TO ALL PLUMBING FIXTURES AND | | | EQUIPMENT UTILIZED FOR BATHING, WASHING, CULINARY | | | PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE. | | | | | | REVIEW BY | | | LARRY WAGNER | | | CHIEF PLUMBING INSPECTOR | | | PHONE # 805-6692 | | | EMAIL [email protected] | | | FAX # 805-6676 | | | |
|