Plan Review Notes
Plan Review Notes For Permit 12030334
Permit Number 12030334
Review Stop P
Sequence Number 1
Notes
Date Text
2012-04-05 11:32:12FBC 2007 PLUMBING REVIEW #1
 DENIED:
  
 1. THE PLUMBING CALCULATIONS ON SHEET G1.0 SHOW 8 WATER
 CLOSETS FOR WOMEN AND 4 FOR MEN. PLEASE CLARIFY OR
 CORRECT THE FOLLOWING:
 1A. SHEET A1.0 AND PLUMBING SHEETS SHOW ONLY 4 WATER
 CLOSETS FOR WOMEN.
 1B. SHEET A1.0 AND PLUMBING SHEETS SHOW 1 WATER CLOSET
 AND 3 URINALS FOR MEN. SECTION 419.2 URINALS SHALL NOT
 BE SUBSTITUTED FOR MORE THAN 67 PERCENT OF THE REQUIRED
 WATER CLOSETS IN ASSEMBLY AND EDUCATIONAL OCCUPANCIES.
 2 WATER CLOSETS AND 2 URINALS WOULD BE REQUIRED.
 1C. 403.7 UNISEX TOILET AND BATHING ROOMS. IN ASSEMBLY
 AND MERCANTILE OCCUPANCIES, AN ACCESSIBLE UNISEX TOILET
 ROOM SHALL BE PROVIDED WHERE AN AGGREGATE OF SIX OR
 MORE MALE AND FEMALE WATER CLOSETS IS REQUIRED.
  
 2. SHEET P-2 HOT WATER WILL BE REQUIRED AT THE JANITOR
 SINK:
 607.1 WHERE REQUIRED. IN OCCUPIED STRUCTURES, HOT WATER
 SHALL BE SUPPLIED TO ALL PLUMBING FIXTURES AND
 EQUIPMENT UTILIZED FOR BATHING, WASHING, CULINARY
 PURPOSES, CLEANSING, LAUNDRY OR BUILDING MAINTENANCE.
  
 REVIEW BY
 LARRY WAGNER
 CHIEF PLUMBING INSPECTOR
 PHONE # 805-6692
 EMAIL [email protected]
 FAX # 805-6676
  