Plan Review Notes
Plan Review Notes For Permit 12030334
Permit Number 12030334
Review Stop M
Sequence Number 1
Notes
Date Text
2012-03-22 11:01:12PLANS DENIED
 1) MISSING FIRE DAMPERS IN STORAGE ROOM 114 C .
 REFER TO SECTION 607.5.1 FIRE WALLS 2007 FBC (M)
 2) PROVIDE INFORMATION ON THE 18X14 DUCT GOING IN THE
 BATHROOM.
 IF IT IS A SUPPLY WHAT RTU IS TI COMING FROM.
 3) REFER TO SECTION 606.2.1 SUPPLY AIR SYSTEM 2007 FBC
 (M)
 AND SECTION 606.4.1 SUPERVISION NEW AND EXISTING RTU.
 4) REFER TO SECTION 13-409.AB.3.3 SHUTOFF DAMPER
 CONTROLS.
 2007 ENERGY CODE.