| 2012-04-03 15:51:57 | 2275 PALM BEACH LAKES BOULEVARD |
| | PERMIT #12030334 |
| | REVIEW COMMENTS - FIRE DEPARTMENT |
| | |
| | UPDATE THE CODE LIST TO REFERENCE THE 2010 EDITION OF |
| | THE FLORIDA FIRE PREVENTION CODE WHICH CONTAINS THE |
| | 2009 EDITION OF BOTH NFPA 1 AND NFPA 101 WITH FLORIDA |
| | AMENDMENTS. |
| | |
| | ALL CONSTRUCTION AND DEMOLITION WORK SHALL CONFORM TO |
| | THE REQUIREMENTS OF NFPA 241. TRASH AND CONSTRUCTION |
| | DEBRIS SHALL BE REMOVED FROM THE SITE DAILY. ALL |
| | DEMOLITION OR CONSTRUCTION AREAS SHALL HAVE "NO |
| | SMOKING" SIGNS POSTED. |
| | |
| | PROVIDE AN EXTERIOR KEY SAFE TO ALLOW EMERGENCY |
| | RESPONDERS NON-FORCIBLE ENTRY INTO THE BUILDING DURING |
| | NON-BUSINESS HOURS. A KEY SAFE CAN BE ORDERED FROM |
| | WWW.KNOXBOX.COM. |
| | |
| | PROVIDE TACTILE SIGNAGE AT ALL REQUIRED EXIT DOORS WITH |
| | EXIT SIGNS. |
| | |
| | THE MAIN ENTRANCE DOORS SHALL BE SIZED TO ACCOMMODATE |
| | 1/2 OF THE MAXIMUM OCCUPANT LOAD. |
| | |
| | FOR OCCUPANCIES WITH AN OCCUPANT LOAD OF 100 OR MORE |
| | PERSONS, PANIC OR FIRE EXIT HARDWARE SHALL BE PROVIDED |
| | ON DOORS TO RELEASE THE LOCK/LATCH. NO OTHER LOCKS OR |
| | LATCHES ARE PERMITTED THAT WOULD NOT BE RELEASED BY THE |
| | PANIC HARDWARE. REFER TO DOOR #3, EX1, EX4 ETC. |
| | |
| | EACH SMOKE OR FIRE-RATED WALL/PARTITION SHALL BE |
| | PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING READING |
| | FIRE/SMOKE BARRIER-PROTECT ALL OPENINGS. CHARACTERS |
| | SHALL BE AT LEAST 4-INCHES IN HEIGHT AND HALF-INCH IN |
| | WIDTH. IDENTIFICATION SHALL BE SPACED NOT MORE THAN 15 |
| | FEET ON CENTER. |
| | |
| | SHEET A10.1 WAS NOT SUBMITTED. |
| | |
| | PER LOCAL AHJ POLICY, DUCT SMOKE DETECTORS SHALL |
| | INITIATE A GENERAL FIRE ALARM CONDITION. |
| | |
| | PROVIDE A PRE-RECORDED FIRE ALARM EVACUATION MESSAGE |
| | NOTIFYING OCCUPANTS AN EMERGENCY HAS BEEN REPORTED IN |
| | THE BUILDING, LOCATE THE NEAREST EXIT, AND EXIT THE |
| | BUILDING IMMEDIATELY. |
| | |
| | A CERTIFICATE OF COMPLETION AND A THIRD PARTY |
| | MONITORING/VERIFICATION (UL OR ETL) CERTIFICATE SHALL |
| | BE PROVIDED AT TIME OF FINAL FIRE ALARM INSPECTION. |
| | |
| | ASSEMBLY OCCUPANCIES EXCEEDING 300 PERSONS WILL BE |
| | REQUIRED TO BE PROTECTED BY AN AUTOMATIC FIRE SPRINKLER |
| | SYSTEM. |
| | |
| | ENGINEERED FIRE SPRINKLER CONSTRUCTION DOCUMENTS ARE |
| | REQUIRED FOR A GENERAL BUILDING PERMIT. AFTER THE |
| | BUILDING PERMIT HAS BEEN ISSUED, THE SUBCONTRACTORS CAN |
| | THEN SUBMIT SHOP DRAWINGS (CONFORMING TO THE ENGINEERED |
| | CONSTRUCTION DOCUMENTS) FOR A SUB-PERMIT. |
| | |
| | |
| | WESLEY JOLIN |
| | OFFICE OF THE FIRE MARSHAL |
| | WEST PALM BEACH FIRE RESCUE |
| | |
| | |