 GROUP A3
  
 VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO
 INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING
 RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND
 CURRENT THAT IS AVAILABLE. NEC 110.9
 FEEDER CONDUCTORS TO NEW PANELBOARDS, OVERCURRENT
 DEVICES AND MAIN LUGS APPEAR TO BE MISMATCHED. LOCATE
 ALL PANEL BOARDS ON THE PLAN SHOWING ALL SAFETY
 CLEARANCES. NEC 310.16, 110.26
 PROVIDE A LIGHTING DENSITY CALCULATION SHOWING
 COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE
 REQUIREMENTS. FBC 13-415 ABC.5
 CLARIFY ON THE PLANS HOW THE LIGHTING WILL BE
 CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES.
 SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS
 13-415 ABC.1.3
  
 NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR
 SECURITY, VOICE, DATA AND FIRE ALARM SYSTEMS.
  