| Notes |
| Date |
Text |
| 2012-03-20 10:07:50 | 12030334 | | | 2275 PALM BEACH LAKES BLVD. | | | SANCTUARY AND CLASSROOMS | | | GROUP A3 | | | | | | VERIFY THAT ALL NEW AND EXISTING EQUIPMENT INTENDED TO | | | INTERRUPT CURRENT AT FAULT LEVELS HAS AN INTERRUPTING | | | RATING SUFFICIENT FOR THE NOMINAL CIRCUIT VOLTAGE AND | | | CURRENT THAT IS AVAILABLE. NEC 110.9 | | | FEEDER CONDUCTORS TO NEW PANELBOARDS, OVERCURRENT | | | DEVICES AND MAIN LUGS APPEAR TO BE MISMATCHED. LOCATE | | | ALL PANEL BOARDS ON THE PLAN SHOWING ALL SAFETY | | | CLEARANCES. NEC 310.16, 110.26 | | | PROVIDE A LIGHTING DENSITY CALCULATION SHOWING | | | COMPLIANCE WITH THE FLORIDA BUILDING ENERGY CODE | | | REQUIREMENTS. FBC 13-415 ABC.5 | | | CLARIFY ON THE PLANS HOW THE LIGHTING WILL BE | | | CONTROLLED USING MOTION SENSORS OR SIMILAR TECHNIQUES. | | | SPACE CONTROL FBC 13-415 ABC.1.2; ADDITIONAL CONTROLS | | | 13-415 ABC.1.3 | | | | | | NOTE: SEPARATE PERMITS AND PLANS ARE REQUIRED FOR | | | SECURITY, VOICE, DATA AND FIRE ALARM SYSTEMS. | | | | | | ROBERT LECKY | | | ELECTRIC PLANS EXAMINER | | | [email protected] | | | 561-805-6718 | | | | | | |
|