| 2012-04-03 13:39:53 | BUILDING PLAN REVIEW |
| | PERMIT: 12030334 |
| | ADD: 2275 PALM BEACH LAKES BLVD |
| | SHILOH FAMILY WORSHIP CENTER - PHASE II |
| | CONT: CUTTING EDGE BUILDING SYSTEMS, INC |
| | TEL: (561)282-8265 |
| | |
| | 2007 FLORIDA BUILDING CODE W/ 2009 FBC SUPPLEMENTS |
| | * WEST PALM BEACH AMENDMENTS |
| | |
| | 2007 EXISTING BUILDING CODE LEVEL II 701.3 |
| | COMPLIANCE. ALL NEW CONSTRUCTION ELEMENTS, COMPONENTS, |
| | SYSTEMS, AND SPACES SHALL COMPLY WITH THE REQUIREMENTS |
| | OF THE FLORIDA BUILDING CODE, BUILDING. |
| | |
| | 1ST REVIEW |
| | ACTION: DENIED |
| | |
| | 1) PLANS SUBMITTED ON MARCH 14/2012 ARE TO BE REVIEWED |
| | UNDER THE 2007/09 FBC. PLANS SUBMITTED ON OR AFTER |
| | MARCH 15TH/ 2012 ARE TO BE REVIEWED UNDER THE 2010 FBC. |
| | SHEET G1.0 GOVERNING CODES INDICATE ALL CONSTRUCTION |
| | WORK, ACTIVITIES & ALTERATIONS SHALL COMPLY WITH THE |
| | 2007 FBC, 2010 EXISTING BUILDING CODE. CODE DESIGNS CAN |
| | NOT BE MIXED BETWEEN THE EDITIONS OF CODES. |
| | |
| | 2) NEITHER G1.0 NOR THE LS1.0 SHEET INDICATE: |
| | 2A) MINIMUM BUILDING TYPE |
| | 2B) IS THIS BUILDING FIRE SPRINKLERED? NEITHER G1.0 NOR |
| | LS1.0 INDICATE FIRE SPRINKLERS, FOR THIS REVIEW IT WILL |
| | BE CONSIDERED NON-SPRIKLERED |
| | 2C) UNDER THE 2007/ 09 EXISTING BUILDING CODE THE |
| | DESIGNER WILL NEED TO PICK A COMPLIANCE METHOD. 2007/09 |
| | EXIST BLDG CODE 101.5. |
| | 2D) IS THIS A CHANGE IN OCCUPANCY FOR THIS SPACE? IF SO |
| | CHAPTER 9 OF THE EXIST BLDG CODE WILL APPLY. 2007/09 |
| | EXIST BLDG CODE 901.3.1 PARTIAL CHANGE IN OCCUPANCY, |
| | SECTION 912 SHALL APPLY. |
| | 2E) LS1.0 SHEET INDICATES ADJACENT TENANT SPACES ON |
| | BOTH SIDES OF THIS TENANT SPACE, THE PLANS INDICATE A |
| | ONE HOUR TENANT SEPERATION WALL, PLEASE REVIEW 2007/09 |
| | FBC-B TABLE 508.3.3 OCCUPANCY SEPERATION FOR EITHER |
| | BUSINESS OR MERCANTILE WITH THIS A3 OCCUPANCY REQUIRES |
| | A 2 HOUR OCCUPANCY SEPERATION WALL. PLEASE NOTE THAT |
| | THE BUSINESS OCCUPANCY THAT TIES TO THIS TENANTCY WOULD |
| | ALSO REQUIRE A 2 HOUR FIRE RATED WALL WITH 1 1/2 HOUR |
| | OPENING PROTECTIVES FBC-B TABLE 715.4. SEE NOTE # 5 ON |
| | SHEET A1.0 FOR A 2 HOUR WALL. |
| | 2F) LS1.0 SHEET DOES NOT INDICATE ANY FIRE RATED |
| | CORRIDORS, PLEASE REVIEW 2007/09 FBC-B TABLE 1017.1THAT |
| | REQUIRES 1 HOUR FIRE RATED CORRIDORS WITH OR WITHOUT |
| | FIRE SPRINKLERS ALSO UPDATE THE DOOR SCHEDULE FOUND ON |
| | SHEET A7.0. |
| | 2G) LS1.0 NOTE # 2 INDICATES A LIMIT OF 299 OCCUPANTS, |
| | PLEASE REVIEW PLANS INDICATE 306 SEATS AND AN OCCUPANT |
| | LOAD OF 21 FOR THE STAGE WHICH TOTALS 327 OCCUPANTS, |
| | WHY THE LIMITING FACTOR TO 299? THE 2007 FBC-B |
| | 903.2.1.3 DOES REQUIRE FIRE SPRINKLERS FOR OCCUPANT |
| | LOADS 300 OR GREATER. |
| | 2H) LS1.0 PLEASE REVIEW FBC-B 907.2.1 FOR ASSEMBLY |
| | AREAS WITH OCCUPANT LOADS OF 300 OR GREATER. |
| | |
| | 3) SHEET A1.0: |
| | 3A) WALL TYPE F IS FOUND AT ALL STORAGE ROOMS WHICH IF |
| | OVER 100 SQ FT WILL REQUIRE A 1 HOUR FIRE RATING TO |
| | EXTEND UP TO THE UNDER SIDE OF THE ROOF DECK FBC-B |
| | 508.2.2.1. |
| | 3B) WALL TYPE B CORRIDOR WALLS WILL ALSO NEED TO BE |
| | UPDATED TO A 1 HOUR FIRE RATED WALL PER FBC-B 708.1( |
| | 4). |
| | |
| | 4) 2007/09 FBC-B 712.6 FIRE WALLS, FIRE BARRIERS, FIRE |
| | PARTITIONS, SMOKE BARRIERS AND SMOKE PARTITIONS OR ANY |
| | OTHER WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE |
| | EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR |
| | STENCILING IN A MANNER ACCEPTABLE TO THE AUTHORITY |
| | HAVING JURISDICTION. SUCH IDENTIFICATION SHALL BE ABOVE |
| | ANY DECORATIVE CEILING AND IN CONCEALED SPACES. |
| | SUGGESTED WORDING FOR FIRE AND SMOKE BARRIERS: "FIRE |
| | AND SMOKE BARRIER - PROTECT ALL OPENINGS." |
| | |
| | 5) SHEET A2.0 INDICATES UNDER SIDE OF CLOUDS PLEASE |
| | PROVIDE DETAILS ON WHAT TYPE OF MATERIALS THIS SYSTEM |
| | IS COMPOSED OF, HOW IT IS TO BE HUNG, AND TO WHAT THE |
| | CLOUD SYSTEM IS TO BE ATTACHED? ADDITIONAL INFORMATION |
| | IS REQUIRED? 106.1.2. |
| | |
| | JAMES A. WITMER CBO |
| | SENIOR COMMERCIAL COMBINATION PLANS EXAMINER |
| | TEL: 561-805-6715 |
| | FAX: 561-805-6676 |
| | E-MAIL: [email protected] |
| | |