| 2012-06-06 20:44:06 | PLANNING: ***** FAILED *****] |
| | |
| | |
| | 1, RESPOND TO COMMENTS IN WRITING WHEN RESUBMITING |
| | DOCUMENTS. |
| | |
| | 2. THE SCOPE OF WORK DENOTES ALL INTERIOR WORK AND |
| | RENOVATIONS, HOWEVER, SHEET E1, PLAN NOTES CALLS OUT |
| | FOR A PROPOSED ASC GENERATOR. THERE ARE NO CIVIL |
| | DRAWINGS THAT SHOW THIS GENERATOR OR ENCLOSURE. IS |
| | THERE A NEW GENERATOR PROPOSED? |
| | |
| | IF SO, PROVIDE THE FOLLOWING INFORMATION: |
| | |
| | A. INDICATE SETBACK DIMENSIONS FROM PROPOSED GENERATOR |
| | EQUIPMENT TO ALL PROPERTY LINES. PURSUANT TO SECTION |
| | 94-305(B)(4) OF THE ZLDR: MECHANICAL EQUIPMENT MAY NOT |
| | PROJECT MORE THAN 4 FEET INTO A REQUIRED SETBACK. |
| | |
| | RESUBMITTAL: DIMENSIONS WERE NOT PROVIDED ON SITE PLAN |
| | SP-1 OR LP-1. |
| | |
| | B. PROVIDE ELEVATIONS AND A FLOOR PLAN OF SCREENING AND |
| | LANDSCAPING DETAIL. INCLUDE WALL HEIGHT, ETC. SCREENING |
| | ENCLOSURE AND LANDSCAPING SHALL MEET SECTION 94-444 OF |
| | THE ZONING AND LAND DEVELOPMENT REGULATIONS. SCREENING |
| | WALLS SHALL BE LANDSCAPED WITH SHRUBS AND HEDGES |
| | PLANTED AT TWO-FOOT INTERVALS. OR PROVIDE INFORMATION |
| | OF EXISTING ENCLOSURE THAT MEETS THE REQUIREMENTS |
| | ABOVE. |
| | |
| | RESUBMITTAL: ELEVATIONS WERE NOT PROVIDED. PROVIDE A |
| | CROSS SECTION OF THE PROPOSED ENCLOSURE, GENERATOR |
| | (INCLUDING THE MOUNTING AND TANK), THE ENTIRE GENERATOR |
| | EQUIPMENT NEEDS TO BE SCREENED FROM VIEW. PROVIDE TOTAL |
| | HEIGHT DIMENSIONS OF FENCE ENCLOSURE AND GENERATOR. |
| | |
| | |
| | |
| | IF YOU HAVE ANY QUESTIONS PLEASE CONTACT ME. |
| | |
| | LINDA MIA FRANCO, AICP |
| | SENIOR PLANNER |
| | PLANNING DIVISION |
| | TEL: (561) 822-1443 |
| | EMAIL: [email protected] |
| | |